SIEMENS
7/126
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Chassis format
Air-cooled Active Line Modules in chassis format
7
Line voltage 380 ... 480 V 3 AC
Active Line Modules
6SL3330-
7TE32-1AA3
6SL3330-
7TE32-6AA3
6SL3330-
7TE33-8AA3
6SL3330-
7TE35-0AA3
6SL3330-
7TE36-1AA3
Rated power
• At
I
rated DC
(50 Hz 400 V)
kW
132
160
235
300
380
• At
I
H DC
(50 Hz 400 V)
kW
115
145
210
270
335
• At
I
rated DC
(60 Hz 460 V)
hp
200
250
400
500
600
• At
I
H DC
(60 Hz 460 V)
hp
150
200
300
400
500
DC link current
• Rated current
I
rated DC
A
235
291
425
549
678
• Base-load current
I
H DC
1)
A
209
259
378
489
603
• Maximum current
I
max DC
A
352
436
637
823
1017
Infeed/regenerative feedback current
• Rated current
I
rated I
A
210
260
380
490
605
• Maximum current
I
max I
A
315
390
570
735
907
Current demand
• 24 V DC auxiliary power supply
A
1.1
1.1
1.35
1.35
1.4
• 400 V AC
A
0.63
1.13
1.8
1.8
3.6
DC link capacitance
• Active Line Module
μ
F
4200
5200
7800
9600
12600
• Drive line-up, max.
μ
F
41600
41600
76800
76800
134400
Power loss, max.
2)
• At 50 Hz 400 V
kW
2.2
2.7
3.9
4.8
6.2
• At 60 Hz 460 V
kW
2.3
2.9
4.2
5.1
6.6
Cooling air requirement
m
3
/s (ft
3
/s)
0.17 (6.0)
0.23 (8.1)
0.36 (12.7)
0.36 (12.7)
0.78 (27.5)
Sound pressure level
L
pA
3)
(1 m) at 50/60 Hz
dB
64/67
71/71
69/73
69/73
70/73
Line connection
U1, V1, W1
Flat connector for
M10 screw
Flat connector for
M10 screw
Flat connector for
M10 screw
Flat connector for
M10 screw
Flat connector for
M12 screw
• Conductor cross section, max. (IEC)
mm
2
2 × 185
2 × 185
2 × 240
2 × 240
4 × 240
DC link connection
DCP, DCN
M10 screw
M10 screw
M10 screw
M10 screw
4 × hole for M12
• Conductor cross section, max. (IEC)
mm
2
2 × 185
2 × 185
2 × 240
2 × 240
Busbar
PE1/GND connection
M10 screw
M10 screw
M10 screw
M10 screw
M12 screw
• Conductor cross section, max. (IEC)
mm
2
2 × 185
2 × 185
2 × 240
2 × 240
240
PE2/GND connection
M10 screw
M10 screw
M10 screw
M10 screw
2 × M12 screw
• Conductor cross section, max. (IEC)
mm
2
2 × 185
2 × 185
2 × 240
2 × 240
2 × 240
Cable length, max.
4)
• Shielded
m (ft)
2700 (8859)
2700 (8859)
2700 (8859)
2700 (8859)
3900 (12796)
• Unshielded
m (ft)
4050 (13288)
4050 (13288)
4050 (13288)
4050 (13288)
5850 (19194)
Degree of protection
IP20
IP20
IP20
IP20
IP00
Dimensions
• Width
mm (in)
326 (12.8)
326 (12.8)
326 (12.8)
326 (12.8)
503 (19.8)
• Height
mm (in)
1400 (55.1)
1400 (55.1)
1533 (60.3)
1533 (60.3)
1475 (58.1)
• Depth
mm (in)
356 (14.0)
356 (14.0)
545 (21.5)
545 (21.5)
540 (21.3)
Weight, approx.
kg (lb)
95 (209)
95 (209)
136 (300)
136 (300)
290 (639)
Frame size
FX
FX
GX
GX
HX
Minimum short-circuit current
5)
A
6200
10500
10500
8000
9200
1)
The base-load current
I
H DC
is the basis for a duty cycle of 150 % for 60 s
or
I
max DC
for 5 s with a duty cycle duration of 300 s.
2)
The specified power loss represents the maximum value at 100 % utilization.
The value is lower under normal operating conditions.
3)
Total sound pressure level of Active Interface Module and Active Line
Module.
4)
Total of all motor cables and DC link. Longer cable lengths for specific
configurations are available on request.
For additional information, please
refer to the SINAMICS Low Voltage Engineering Manual
.
5)
Current required for reliably triggering protective devices.
■
Technical specifications
(continued)
© Siemens AG 2017