Overview
Motor reactors reduce the voltage loading on the motor wind-
ings. At the same time, the capacitive charge/discharge cur-
rents that place an additional load on the power unit when long
motor cables are used are reduced. The maximum permissible
output frequency when a motor reactor is used is 120 Hz.
The motor reactors are designed for a pulse frequency of 4 kHz.
Higher pulse frequencies are not permissible.
The motor reactor must be installed as close as possible to the
Motor Module.
■
Selection and ordering data
Rated output
current of
Motor Module
Suitable for
Motor Module
in booksize format
Motor reactor
Article No.
3 A and 2 × 3 A
6SL3120-1TE13-0AD0
6SL3120-2TE13-0AD0
6SE7021-0ES87-1FE0
5 A and 2 × 5 A
6SL3120-1TE15-0AD0
6SL3120-2TE15-0AD0
6SE7021-0ES87-1FE0
9 A and 2 × 9 A
6SL3120-1TE21-0AD0
6SL3120-2TE21-0AD0
6SL3000-2BE21-0AA0
18 A and
2 × 18 A
6SL3120-1TE21-8AC0
6SL3120-1TE21-8AD0
6SL3120-2TE21-8AC0
6SL3120-2TE21-8AD0
6SE7022-6ES87-1FE0
30 A
6SL3120-1TE23-0AC0
6SL3120-1TE23-0AD0
6SE7024-7ES87-1FE0
45 A
6SL3120-1TE24-5AA3
6SE7027-2ES87-1FE0
60 A
6SL3120-1TE26-0AA3
6SL3000-2BE26-0AA0
85 A
6SL3120-1TE28-5AA3
6SE7031-5ES87-1FE0
132 A
6SL3120-1TE31-3AA3
6SE7031-8ES87-1FE0
200 A
6SL3120-1TE32-0AA4
6SE7032-6ES87-1FE0
© Siemens AG 2017