SIEMENS
7/66
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Booksize format
Single Motor Modules in booksize compact format
7
■
Selection and ordering data
■
Technical specifications
Rated output
current
Type rating
3)
Single Motor Module
in booksize compact format
A
kW (hp)
Article No.
DC link voltage 510 ... 720 V DC
3
1.6 (1.5)
6SL3420-1TE13-0AA1
5
2.7 (3)
6SL3420-1TE15-0AA1
9
4.8 (5)
6SL3420-1TE21-0AA1
18
9.7 (10)
6SL3420-1TE21-8AA1
Description
Article No.
Accessories
DC link rectifier adapter
For direct infeed of DC link voltage
Screw-type terminals 0.5 ... 10 mm
2
For Line Modules and Motor Modules
in booksize format with a width of 50 mm
(1.97 in), 75 mm (2.95 in) and 100 mm
(3.94 in)
6SL3162-2BD00-0AA0
DC link adapter
(2 units)
For multi-tier configuration
Screw-type terminals 35 ... 95 mm
2
For all Line Modules and Motor Modules
in booksize format
6SL3162-2BM01-0AA0
24 V terminal adapter
For all Line Modules and Motor Modules
in booksize format
6SL3162-2AA00-0AA0
Spacing bolt
(4 units)
The mounting depth of modules in booksize
compact format is increased when it is
mounted on these spacing bolts by such an
amount that it can be integrated into a drive
line-up in booksize format. 2 spacing bolts
are required to mount 50 mm (1.97 in) wide
modules, and 4 spacing bolts for 75 mm
(2.95 in) wide modules.
6SL3462-1CC00-0AA0
Accessories for re-ordering
24 V jumper
For connection of the 24 V busbars
(for booksize format)
6SL3162-2AA01-0AA0
Warning labels in 30 languages
This label set can be glued over the
standard German or English labels to
provide warnings in other languages.
One set of labels is supplied with the
devices.
One sign in each of the following languages
is provided in each set:
BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB,
GR, HU, IE, IS, IT, JP, KR, LT, LV, MT, NL,
NO, PL, PT, RO, RU, SE, SI, SK, TR
6SL3166-3AB00-0AA0
Dust protection blanking plugs
(50 units)
For DRIVE-CLiQ port
6SL3066-4CA00-0AA0
Single Motor Module
in booksize compact format
6SL3420-1TE...
DC link voltage
(up to 2000 m (6562 ft)
above sea level)
510 ... 720 V DC
(line voltage 380 ... 480 V 3 AC)
Output frequency
• Control mode Servo
0 ... 650 Hz
1) 2)
• Control mode Vector
0 ... 300 Hz
1)
• Control mode V/f
0 ... 600 Hz
1) 2)
Electronics power supply
24 V DC -15 %/+20 %
Type of cooling
Internal air cooling (power units with
increased air cooling by built-in fan)
Permissible ambient and
coolant temperature (air)
during operation for line-side
components, Line Modules and
Motor Modules
0 ... 40 °C (32 ... 104 °F)
without derating,
> 40 ... 55 °C (104 ... 131 °F),
see derating characteristics
Installation altitude
Up to 1000 m (3281 ft)
above sea level without derating,
> 1000 ... 4000 m (3281 ... 13124 ft)
above sea level,
see derating characteristics
Declarations of conformity
CE
(Low Voltage and EMC Directives)
Certificate of suitability
UL-recognized
Safety Integrated
Safety Integrity Level 2 (SIL 2) acc. to
IEC 61508, Performance Level d
(PL d) acc. to ISO 13849-1 and
Control Category 3 acc. to
ISO 13849-1 or EN 954-1
For further information, see section
Safety Integrated.
.
1)
Note the correlation between max. output frequency, pulse frequency and
current derating.
For further information, see section configuration notes.
2)
The output frequency is currently limited to 550 Hz. The specified values
apply to systems with license for high output frequency.
For further information, see section Control Units and
3)
Nominal hp ratings based on asynchronous (induction) motors. Match the
motor nameplate current for specific sizing.
© Siemens AG 2017