SIEMENS
7/62
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Booksize format
Line filters for Basic Line Modules
7
■
Overview
In plants with strict EMC requirements, line filters work together
with line reactors to restrict the conducted interference emanating
from the power modules to the limit values of Class A1 as defined
in EN 55011 and Category C2 as defined in EN 61800-3. Line
filters are only suitable for direct connection to TN line systems.
■
Selection and ordering data
■
Technical specifications
Rated power
of the Basic
Line Module
Suitable for
Basic Line Module
in booksize format
Line filter
kW (hp)
Article No.
Line voltage 380 ... 480 V 3 AC
20 (25)
6SL3130-1TE22-0AA0
6SL3000-0BE21-6DA0
40 (60)
6SL3130-1TE24-0AA0
6SL3000-0BE23-6DA1
100 (125)
6SL3130-1TE31-0AA0
6SL3000-0BE31-2DA0
Line voltage 380 ... 480 V 3 AC
Line filter
6SL3000-0BE21-6DA0
6SL3000-0BE23-6DA1
6SL3000-0BE31-2DA0
Rated current
A
36
74
192
Power loss
kW
0.016
0.026
0.043
Line/load connection
L1, L2, L3 / U, V, W
Screw-type terminals
Screw-type terminals
Screw-type terminals
• Conductor cross-section
mm
2
10
35
95
PE connection
M6 screw stud
M6 screw stud
M10 screw stud
Degree of protection
IP20
IP20
IP20
Dimensions
• Width
mm (in)
50 (1.97)
75 (2.95)
150 (5.91)
• Height
mm (in)
429 (16.89)
433 (17.05)
479 (18.86)
• Depth
mm (in)
226 (8.90)
226 (8.90)
226 (8.90)
Weight, approx.
kg (lb)
5 (11.3)
7.5 (16.5)
18.5 (40.8)
Certificate of suitability
cURus
cURus
cURus
Suitable for
Basic Line Module
in booksize format
Type
6SL3130-1TE22-0AA0
6SL3130-1TE24-0AA0
6SL3130-1TE31-0AA0
• Rated power of the
Basic Line Module
kW (hp)
20 (25)
40 (50)
100 (125)
© Siemens AG 2017