SIEMENS
7/43
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Booksize format
Smart Line Modules in booksize compact format
7
■
Technical specifications
Smart Line Module
in booksize compact format
6SL3430-6TE21-6AA1
Line voltage
(up to 2000 m (6562 ft)
above sea level)
380 ... 480 V 3 AC ±10 %
(in operation -15 % <1 min)
Line frequency
47 ... 63 Hz
SCCR
(short-circuit current rating)
65 kA in conjunction with the
recommended Class J fuse,
or circuit breaker according to
UL489 / CSA 22.2 No. 5-02
see recommended line-side
components
Line power factor
at rated power
• Fundamental (cos
ϕ
1
)
>0.96
• Total (
λ
)
0.65 ... 0.9
Overvoltage category
according to EN 60664-1
Class III
DC link voltage, approx.
1.35 × line voltage
1)
Electronics power supply
24 V DC, -15 %/+20 %
Radio interference suppression
• Standard
No radio interference suppression
• With line filter
Category C2 to EN 61800-3
Total cable length up to 350 m
(1148 ft) (shielded)
Type of cooling
Internal air cooling (power units with
increased air cooling by built-in fan)
Permissible ambient and
coolant temperature (air)
during operation for line-side
components, Line Modules and
Motor Modules
0 ... 40 °C (32 ... 104 °F)
without derating,
> 40 ... 55 °C (104 ... 131 °F),
see derating characteristics
Installation altitude
Up to 1000 m (3281 ft) above sea
level without derating,
> 1000 ... 4000 m (3281 ... 13124 ft)
above sea level,
see derating characteristics
Declarations of conformity
CE
(Low Voltage and EMC Directives)
Certificate of suitability
UL recognized
Line voltage 380 ... 480 V 3 AC
Smart Line Module
in booksize compact format
Internal air cooling
6SL3430-6TE21-6AA1
Infeed/regenerative feedback power
• Rated power
P
rated
-
At 380 V 3 AC
16 kW
-
At 460 V 3 AC
3)
(18 hp)
• For S6 duty (40 %)
P
S6
21 kW
•
P
max
35 kW
DC link current
• At 600 V DC
27 A
• For S6 duty (40 %)
35 A
• Maximum
59 A
Input current
• Rated current at 380 V 3 AC
29 A
• For S6 duty (40 %)
35 A
• Maximum
57.5 A
Current requirement
24 V DC electronics power supply,
max.
1.1 A
Current carrying capacity
• 24 V DC busbars
20 A
• DC link busbars
100 A
DC link capacitance
• Smart Line Module
705
μ
F
• Drive line-up, max.
6000
μ
F
Power loss
2)
0.19 kW
Cooling air requirement
0.016 m
3
/s
Sound pressure level
L
pA
(1 m)
<60 dB
Line connection
U1, V1, W1
Screw-type terminals (X1)
• Conductor cross-section, max.
2.5 ... 10 mm
2
Shield connection
Cable shield connection plate
integrated into the connector
PE connection
M5 screw
Cable length, max.
(total of all motor cables and DC link)
• Shielded
630 m (2067 ft)
• Unshielded
850 m (2788 ft)
Degree of protection
IP20
Dimensions
• Width
100 mm (3.94 in)
• Height
270 mm (10.63 in)
• Depth
226 mm (8.90 in)
Weight, approx.
5.3 kg (11.7 lb)
1)
The DC link voltage is regulated to the mean value of the rectified line
voltage.
For further information, see section configuration notes.
2)
Power loss of Smart Line Module at rated output including losses of
24 V DC electronics power supply.
3)
Nominal hp ratings are provided for ease of assigning components only.
The Line Module outputs are dependent on the Motor Module loading and
are to be dimensioned accordingly.
© Siemens AG 2017