SIEMENS
4/13
Siemens D 15.1 · 2017
Description of Options
Description of options
4
■
Options
(continued)
U12
Redundant single cell
This option is to provide the ability for only a single cell in a drive
to fail without the drive faulting or losing its full output power
capability.
For detailed information, please contact the factory or your local
Siemens sales representative.
Note:
Option
U12
requires that option
U11
(cell bypass) is also
ordered.
U13
Redundant rank of cells
This option is to provide the ability for one cell in each phase of
a drive to fail without the drive faulting or losing its full output
power capability.
For detailed information, please contact the factory or your local
Siemens sales representative.
Note:
Option
U13
requires that option
U11
(cell bypass) is also
ordered.
V01 to V14
Motor voltages
The motor voltage can be selected with options
V01
to
V14
.
These options are mutually exclusive. Select one of them.
Y05
Customer-specific nameplate
As standard the nameplate shows the rated data of the drive
under nominal conditions.
If data on the nameplate should be adapted to special ambient
conditions (temperature, altitude) or should reflect special load
conditions (e.g. derating because of operation at low fre-
quency), then option
Y05
must be selected.
Information to be supplied:
• Altitude
•
Coolant temperature
•
Rated voltage
•
Rated current
•
Rated power
Y09
Paint finish other than standard
As standard the drives are supplied with an RAL 7035 paint
finish. A special color must be specified in plain text when
ordering.
Note:
The cover of the filter mats also has the standard RAL 7035 color
even though the cabinet has a special paint finish.
Y10
Circuit diagrams (German/English) with customer-specific
description field
As standard, the circuit diagrams are in German/English and
can be provided with customer-specific headers. The header
must be specified in plain text (up to three lines of 45 characters
per line).
Option
Motor voltage
V01
2.3 kV
V02
2.4 kV
V03
3.0 kV
V04
3.3 kV
V05
4.0 kV
V06
4.16 kV
V07
4.8 kV
V08
5.0 kV
V09
5.5 kV
V10
6.0 kV
V11
6.3 kV
V12
6.6 kV
V13
6.9 kV
1)
V14
7.2 kV
1)
1)
Only for 6SR4... drives, motor voltages 6.0 and 6.6 kV.
© Siemens AG 2017