SIEMENS
3/7
Siemens D 15.1 · 2017
Technical Data
SINAMICS PERFECT HARMONY GH180, article number 6SR4...
3
■
Technical data
(continued)
SINAMICS PERFECT HARMONY GH180
air-cooled drive version
6SR4102-
0.C35-0..0
6SR4102-
0.C36-0..0
6SR4102-
0.C37-0..0
6SR4102-
0.D37-0..0
6SR4102-
0.D38-0..0
6SR4102-
0.D38-7..0
Motor voltage 3.3 kV
Max. output voltage
kV
4.2
4.2
4.2
4.2
4.2
4.2
Type rating
kVA
450
540
570
630
720
800
Shaft output
1)
kW
373
448
473
522
597
662
hp
500
600
634
700
800
887
Typical motor current
1)
A
79
95
100
110
126
140
Power cell current
A
100
100
100
140
140
140
Number of cells
9
9
9
9
9
9
Aluminum transformer available
Yes
2)
Yes
2)
Yes
2)
Yes
2)
On request
On request
Power loss of drive system
• with copper transformer
kW
< 14
< 16
< 17
< 19
< 21
< 24
• with aluminum transformer
kW
< 15
< 18
< 19
< 21
–
–
Efficiency
P
out
/
P
in
3)
of drive system
• with copper transformer
%
96.5
96.5
96.5
96.5
96.5
96.5
• with aluminum transformer
%
96
96
96
96
–
–
Auxiliary supply
• Single-phase w/o options
4)
kVA
< 1.5
< 1.5
< 1.5
< 1.5
< 1.5
< 1.5
• Single-phase w/ all options
4)
kVA
< 3
< 3
< 3
< 3
< 3
< 3
• Three-phase w/o CPT
5)
kVA
< 4
< 4
< 4
< 4
< 4
< 4
• Three-phase w/ CPT and all
options
5)
kVA
< 7
< 7
< 7
< 7
< 7
< 7
Cooling medium flow rate
m
3
/s
2.2
2.2
2.2
2.2
2.2
2.2
CFM
4700
4700
4700
4700
4700
4700
Sound pressure level
L
pA
(1 m)
dB (A)
80
80
80
80
80
80
Power cabling cross-sections
• Cable cross-sections,
line-side, max. connectable per
phase
6)
AWG/MCM
(NEC, CEC)
1 x 250 MCM
1 x 250 MCM
1 x 250 MCM
1 x 250 MCM
1 x 250 MCM
1 x 250 MCM
mm
2
(DIN VDE)
1 x 120
1 x 120
1 x 120
1 x 120
1 x 120
1 x 120
• Cable cross-sections,
motor-side, max. connectable
per phase
6)
AWG/MCM
(NEC, CEC)
1 x 250 MCM
1 x 250 MCM
1 x 250 MCM
1 x 250 MCM
1 x 250 MCM
1 x 250 MCM
mm
2
(DIN VDE)
1 x 120
1 x 120
1 x 120
1 x 120
1 x 120
1 x 120
• PE connection,
max. connection cross-section
at enclosure
6)
AWG/MCM
(NEC, CEC)
2/0 AWG
2/0 AWG
2/0 AWG
2/0 AWG
2/0 AWG
2/0 AWG
mm
2
(DIN VDE)
70
70
70
70
70
70
Degree of protection
NEMA1/IP21
NEMA1/IP21
NEMA1/IP21
NEMA1/IP21
NEMA1/IP21
NEMA1/IP21
Drive dimensions (transformer cabinet and cell cabinet)
• Width
mm
1680
1680
1680
1680
1680
1680
in
66
66
66
66
66
66
• Height (incl. blowers)
mm
2812
2812
2812
2812
2812
2812
in
111
111
111
111
111
111
• Depth
mm
1065
1065
1065
1065
1065
1065
in
42
42
42
42
42
42
• Schematic drawing
7)
A
A
A
A
A
A
Drive weight (transformer cabinet and cell cabinet)
• Weight, approx.
kg
2700
2900
3100
3100
3300
3400
lb
5950
6390
6830
6830
7280
7500
1)
The specifications for the typical motor current and the power data in kW and hp are approximate values only; these have been calculated for operation with
induction motors and for a typical power factor cos
and motor efficiency. Both approximate values have to be adapted to the motor that is actually used.
2)
For primary voltages > 7.2 kV, please contact the factory or your local Siemens sales representative.
3)
Values at 100 % of rated speed and torque; includes drive and input transformer.
4)
120/240 V AC for NXGpro control
- 6SR4... drives derive single-phase control power from a built-in CPT as standard.
- For 6SR4... drives, customers can directly connect single-phase control power as an option (
K68
).
- CPT is an option in other systems.
5)
Includes cooling blowers/pumps; data refers to the largest unit.
6)
Maximum installable size per phase.
7)
Please refer to page 3/3
for schematic drawings.
© Siemens AG 2017