![](https://www.globalindustrialsupplies.eu/wp-content/uploads/2016/08/siemens-gallery-4-324x200.jpg)
7/11
Siemens D 31 · 2015
7
SINAMICS G110D distributed inverters
0.75 kW to 7.5 kW (1 hp to 10 hp)
SINAMICS G110D distributed inverters
■
Characteristic curves
Derating data
Pulse frequency
Ambient temperature
Permissible output current as a function of ambient temperature for
frame sizes FSA to FSC
Installation altitude
Permissible output current as a function of installation altitude for
frame sizes FSA to FSC
Permissible input voltage as a function of installation altitude for
frame sizes FSA to FSC
1)
It is not possible to make any assignment to a particular standard.
Rated power
at 400 V 3 AC
Rated output current in A
for a pulse frequency of
kW
hp
4 kHz
6 kHz
8 kHz
10 kHz
12 kHz
14 kHz
16 kHz
0.75
1
2.2
1.9
1.5
1.3
1.1
1
0.9
1.5
1.5
1)
4.1
3.5
2.9
2.5
2.1
1.8
1.6
3
4
7.7
6.5
5.4
4.6
3.9
3.5
3.1
4
5
10.2
8.7
7.1
6.1
5.1
4.6
4.1
5.5
7.5
13.2
11.2
9.2
7.9
6.6
5.9
5.3
7.5
10
19
16.2
13.3
11.4
9.5
8.6
7.6
0
20
30
10
40
-10
50 °C
60
75
%
50
25
100
55
55
G_D011_EN_00124
Ambient temperature
Permissible
output current
(32)
(68)
(86)
(50)
(104)
(14)
(122)(°F)
(140)
(131)
G_D011_EN_00203
Permissible
output current
Installation altitude above sea level
(ft)
(13124)
(9843)
(6562)
(3281)
60
90
70
m
4000
3000
2000
1000
0
%
100
80
84
75
G_D011_EN_00204
Permissible
input voltage
Installation altitude above sea level
(ft)
(3281)
(6562)
(9843)
(13124)
60
90
70
m
4000
3000
2000
1000
0
%
100
80
88
78
© Siemens AG 2014