SIEMENS
5/82
Siemens D 31 N · March 2016
SINAMICS G120 standard inverters
0.37 kW to 250 kW (0.5 hp to 400 hp)
Power Modules
5
■
Dimensional drawings
PM230 Power Modules, degree of protection IP20, and PM240-2 Power Modules, push-through variants
Principle dimension drawing and drill pattern for PM230 Power Modules, degree of protection IP20, push-through variant, with/without integrated line
filter class A and PM240-2 Power Modules, push-through variant, with/without integrated line filter class A
Frame
size
Dimensions
in mm
(inches)
Drilling dimensions
in mm
(inches)
Section of cabinet
in mm
(inches)
Cooling clearance
in mm
(inches)
Mounting
a
(width)
b
(height)
c
(depth)
1)
d
e
f
g
(width)
h
(height)
top
bottom
side
2)
With bolts
PM230 and PM240-2 Power Modules, degree of protection IP20, push-through variant, with/without integrated line filter class A
FSA
125.9
(4.96)
238
(9.37)
171
(6.73)
106
(4.17)
103
(4.06)
27
(1.06)
88
(3.46)
198
(7.8)
80
(3.15)
100
(3.94)
0
(0)
M5
FSB
153.9
(6.06)
345
(13.58)
171
(6.73)
134
(5.28)
147.5
(5.81)
34.5
(1.36)
116
(4.57)
304
(11.97)
80
(3.15)
100
(3.94)
0
(0)
M5
FSC
200
(7.87)
410.5
(16.16)
171
(6.73)
174
(6.85)
123
(4.84)
30.5
(1.2)
156
(6.14)
365
(14.37)
80
(3.15)
100
(3.94)
0
(0)
M5
G_D011_EN_00387a
c
e
e
h
f
f
g
b
a
d
Control
cabinet
Control
cabinet
Rear
view
Drill pattern
and
section
e
e
e
h
f
f
g
b
a
d
Control
cabinet
Rear
view
Drill pattern
and
section
FSA, FSB
FSC
1)
Overall depth, of which 117.7 mm
(4.63 in)
is inside and 53.1 mm
(2.09 in)
is outside the control cabinet. Increased depth:
• When the CU230P-2 Control Unit is plugged on, the depth increases by
58 mm
(2.28 in)
• When the CU240B-2 or CU240E-2 Control Unit is plugged on, the depth
increases by 40 mm
(1.57 in)
• When the CU250S-2 Control Unit is plugged on, the depth increases by
61 mm
(2.4 in)
.
• When the IOP is plugged on, the depth increases by a further 22 mm
(0.87 in)
• When the BOP-2 is plugged on, the depth increases by a further 12 mm
(0.47 in)
2)
The Power Modules can be mounted side by side (mounting frame to
mounting frame). A side clearance of 1 mm
(0.04 in)
is recommended for
tolerance-related reasons.
© Siemens AG 2016