SIEMENS
5/81
Siemens D 31 N · March 2016
SINAMICS G120 standard inverters
0.37 kW to 250 kW (0.5 hp to 400 hp)
Power Modules
5
■
Dimensional drawings
PM230 Power Modules, degree of protection IP20, and PM240-2 Power Modules, standard versions
Principle dimension drawing and drill pattern for PM230 Power Modules, degree of protection IP20, standard variant, with/without integrated line filter
class A and PM240-2 Power Modules, standard variant, with/without integrated line filter class A
Frame size
Dimensions
in mm
(inches)
Drilling dimensions
in mm
(inches)
Cooling clearance
2)
in mm
(inches)
Mounting
a
(width)
b
(height)
c
(depth)
1)
d
e
f
top
bottom
front
With bolts
PM230 Power Modules, degree of protection IP20, standard variant, with/without integrated line filter class A
FSA
73
(2.87)
196
(7.72)
165
(6.5)
62.3
(2.45)
186
(7.32)
6
(0.24)
80
(3.15)
100
(3.94)
0
(0)
3 × M4
FSB
100
(3.94)
292
(11.5)
165
(6.5)
80
(3.15)
281
(11.06)
6
(0.24)
80
(3.15)
100
(3.94)
0
(0)
4 × M4
FSC
140
(5.51)
355
(13.98)
165
(6.5)
120
(4.72)
343
(13.5)
6
(0.24)
80
(3.15)
100
(3.94)
0
(0)
4 × M5
FSD
275
(10.83)
419/512
(16.50/20.16
)
204
(8.03)
235
(9.25)
325/419
(12.8/16.5)
11
(0.43)
300
(11.81)
300
(11.81)
0
(0)
4 × M6
FSE
275
(10.83)
499/635
(19.65/25)
204
(8.03)
235
(9.25)
405/541
(15.94/21.3)
11
(0.43)
300
(11.81)
300
(11.81)
0
(0)
4 x M6
FSF
350
(13.78)
634/934
(24.96/36.77
)
316
(12.44)
300
(11.81)
598/899
(23.54/35.39
)
11
(0.43)
350
(13.78)
350
(13.78)
0
(0)
4 × M8
PM240-2 Power Modules, standard variant, with/without integrated line filter class A
FSA
73
(2.87)
196
(7.72)
165
(6.5)
62.3
(2.45)
186
(7.32)
6
(0.24)
80
(3.15)
100
(3.94)
0
(0)
3 × M4
FSB
100
(3.94)
291
(11.46)
165
(6.5)
80
(3.15)
281
(11.06)
6
(0.24)
80
(3.15)
100
(3.94)
0
(0)
4 × M4
FSC
140
(5.51)
355
(13.98)
165
(6.5)
120
(4.72)
343
(13.5)
6
(0.24)
80
(3.15)
100
(3.94)
0
(0)
4 × M5
FSD
200
(7.87)
472
(18.58)
237
(9.33)
170
(6.69)
430
(16.93)
7
(0.28)
300
(11.81)
350
(13.78)
100
(3.94)
4 × M5
FSE
275
(10.83)
551
(21.69)
237
(9.33)
230
(9.06)
509
(20.04)
8.5
(0.33)
300
(11.81)
350
(13.78)
100
(3.94)
4 x M6
FSF
305
(12.01)
709
(27.9)
357
(14.06)
270
(10.63)
680
(26.77)
13
(0.51)
300
(11.81)
350
(13.78)
100
(3.94)
4 × M8
d
e
f
f
d
a
c
e
G_D011_EN_00388
Drill
pattern
FSA
b
Drill pattern
FSB - FSF
1)
Increased depth:
• When the CU230P-2 Control Unit is plugged on, the depth increases by
-
58 mm
(2.28 in)
for frame sizes FSA to FSC
-
49 mm
(1.93 in)
for PM230 with frame sizes FSD to FSF
-
16 mm
(0.63 in)
for PM240-2 with frame sizes FSD to FSF
• When the CU240B-2 or CU240E-2 Control Unit is plugged on, the depth
increases by
-
40 mm
(1.57 in)
for frame sizes FSA to FSC
-
31 mm
(1.22 in)
for PM230 with frame sizes FSD to FSF
-
0 mm
(0 in)
for PM240-2 with frame sizes FSD to FSF
• When the CU250S-2 Control Unit is plugged in, the depth increases by
-
61 mm
(2.4 in)
for frame sizes FSA to FSC
-
52 mm
(2.05 in)
for PM230 with frame sizes FSD to FSF
-
19 mm
(0.75 in)
for PM240-2 with frame sizes FSD to FSF
• When the IOP is plugged on, the depth increases by a further 22 mm
(0.87 in)
• When the BOP-2 is plugged on, the depth increases by a further 12 mm
(0.47 in)
2)
The Power Modules can be mounted side by side. A side clearance of
1 mm
(0.04 in)
is recommended for tolerance-related reasons.
© Siemens AG 2016