SIEMENS
5/110
Siemens D 31 N · March 2016
SINAMICS G120 standard inverters
0.37 kW to 250 kW (0.5 hp to 400 hp)
Load-side power components
> Output reactors
5
■
Technical specifications
Line voltage 380 ... 480 V 3 AC
Output reactor (for a 4 kHz pulse frequency)
6SE6400-
3TC14-5FD0
6SE6400-
3TC15-4FD0
6SE6400-
3TC14-5FD0
6SL3000-
2BE32-1AA0
6SL3000-
2BE32-6AA0
Rated current
A
178
1)
178
1)
178
1)
210
260
Power loss
kW
0.47
0.25
0.47
0.49
0.5
Connection to the Power Module
Flat connector for
M8 cable lug
Flat connector for
M8 cable lug
Flat connector for
M8 cable lug
Flat connector for
M10 screw
Flat connector for
M10 screw
Motor connection
Flat connector for
M8 cable lug
Flat connector for
M8 cable lug
Flat connector for
M8 cable lug
Flat connector for
M10 screw
Flat connector for
M10 screw
PE connection
M8 screw
M6 screw
M8 screw
M8 screw
M8 screw
Cable length, max.
between output reactor and motor
• 380 -10 % ... 400 V 3 AC
- Shielded
m (ft)
200 (656)
200 (656)
200 (656)
200 (656)
200 (656)
- Unshielded
m (ft)
300 (984)
300 (984)
300 (984)
300 (984)
300 (984)
• 401 ... 480 V 3 AC +10 %
- Shielded
m (ft)
200 (656)
200 (656)
200 (656)
200 (656)
200 (656)
- Unshielded
m (ft)
300 (984)
300 (984)
300 (984)
300 (984)
300 (984)
Dimensions
• Width
mm (in)
350 (13.78)
270 (10.63)
350 (13.78)
300 (11.81)
300 (11.81)
• Height
mm (in)
321 (12.64)
248 (9.76)
321 (12.64)
285 (11.22)
315 (12.40)
• Depth
mm (in)
288 (11.34)
209 (8.23)
288 (11.34)
257 (10.12)
277 (10.91)
Degree of protection
IP00
IP00
IP00
IP00
IP00
Weight, approx.
kg (lb)
51.5 (114)
24 (52.9)
51.5 (114)
60 (132)
66 (145)
Suitable for
PM230 Power Module
degree of protection IP20
Type
6SL3210-
1NE31-1UL0
6SL3210-
1NE31-1AL0
6SL3210-
1NE31-5UL0
6SL3210-
1NE31-5AL0
–
–
–
Suitable for
PM250 Power Module
Type
6SL3225-
0BE34-5 . A0
6SL3225-
0BE35-5 . A0
6SL3225-
0BE37-5 . A0
–
–
• Rated power of the
Power Module
kW (hp)
55 (75)
75 (100)
90 (125)
110 (150)
132 (200)
• Rated current
I
rated
of the
Power Module
A
110
145
178
205
250
• Frame size
FSF
FSF
FSF
FSF
FSF
1)
On the rating plate of the reactor the current is specified according to
the duty cycle for high overload (HO). This is lower than the current
specified according to the duty cycle for low overload (LO) of the
Power Module.
© Siemens AG 2016