SIEMENS
5/109
Siemens D 31 N · March 2016
SINAMICS G120 standard inverters
0.37 kW to 250 kW (0.5 hp to 400 hp)
Load-side power components
> Output reactors
5
■
Technical specifications
Line voltage 380 ... 480 V 3 AC
Output reactor (for a 4 kHz pulse frequency)
6SE6400-
3TC05-4DD0
6SE6400-
3TC03-8DD0
6SE6400-
3TC05-4DD0
6SE6400-
3TC08-0ED0
6SE6400-
3TC07-5ED0
Rated current
A
68
1)
45
1)
68
1)
104
1)
90
1)
Power loss
kW
0.2
0.2
0.2
0.17
0.27
Connection to the Power Module
Flat connector for
M6 cable lug
Flat connector for
M6 cable lug
Flat connector for
M6 cable lug
Flat connector for
M6 cable lug
Flat connector for
M6 cable lug
Motor connection
Flat connector for
M6 cable lug
Flat connector for
M6 cable lug
Flat connector for
M6 cable lug
Flat connector for
M6 cable lug
Flat connector for
M6 cable lug
PE connection
M6 screw
M6 screw
M6 screw
M6 screw
M6 screw
Cable length, max.
between output reactor and motor
• 380 -10 % ... 400 V 3 AC
- Shielded
m (ft)
200 (656)
200 (656)
200 (656)
200 (656)
200 (656)
- Unshielded
m (ft)
300 (984)
300 (984)
300 (984)
300 (984)
300 (984)
• 401 ... 480 V 3 AC +10 %
- Shielded
m (ft)
200 (656)
200 (656)
200 (656)
200 (656)
200 (656)
- Unshielded
m (ft)
300 (984)
300 (984)
300 (984)
300 (984)
300 (984)
Dimensions
• Width
mm (in)
225 (8.86)
225 (8.86)
225 (8.86)
225 (8.86)
270 (10.63)
• Height
mm (in)
210 (8.27)
210 (8.27)
210 (8.27)
210 (8.27)
248 (9.76)
• Depth
mm (in)
150 (5.91)
179 (7.05)
150 (5.91)
150 (5.91)
209 (8.23)
Degree of protection
IP00
IP00
IP00
IP00
IP00
Weight, approx.
kg (lb)
10.7 (23.6)
16.1 (35.5)
10.7 (23.6)
10.4 (22.9)
24.9 (54.9)
Suitable for
PM230 Power Module
degree of protection IP20
Type
–
6SL3210-
1NE24-5UL0
6SL3210-
1NE24-5AL0
6SL3210-
1NE26-0UL0
6SL3210-
1NE26-0AL0
6SL3210-
1NE27-5UL0
6SL3210-
1NE27-5AL0
6SL3210-
1NE28-8UL0
6SL3210-
1NE28-8AL0
Suitable for
PM250 Power Module
Type
6SL3225-
0BE31-5 . A0
6SL3225-
0BE31-8 . A0
6SL3225-
0BE32-2 . A0
6SL3225-
0BE33-0 . A0
6SL3225-
0BE33-7 . A0
• Rated power of the
Power Module
kW (hp)
18.5 (25)
22 (30)
30 (40)
37 (50)
45 (60)
• Rated current
I
rated
of the
Power Module
A
38
45
60
75
90
• Frame size
FSD
FSD
FSD
FSE
FSE
1)
On the rating plate of the reactor the current is specified according to
the duty cycle for high overload (HO). This is lower than the current
specified according to the duty cycle for low overload (LO) of the
Power Module.
© Siemens AG 2016