SIEMENS
5/77
Siemens D 31 N · March 2016
SINAMICS G120 standard inverters
0.37 kW to 250 kW (0.5 hp to 400 hp)
Power Modules
5
■
Characteristic curves
Derating data, PM240-2 Power Modules
Pulse frequency
Rated power
1)
at 50 Hz 200 V 1 AC/3 AC
Rated output current in A
for a pulse frequency of
kW
hp
4 kHz
6 kHz
8 kHz
10 kHz
12 kHz
14 kHz
16 kHz
0.55
0.75
3.2
2.6
2.1
1.8
1.5
1.4
1.2
0.75
1
4.2
3.3
2.7
2.3
2
1.8
1.6
1.1
1.5
6
4.7
3.9
3.3
2.8
2.5
2.2
1.5
2
7.4
6.3
5.2
4.4
3.7
3.3
3
2.2
3
10.4
8.8
7.3
6.2
5.2
4.7
4.2
3
4
13.6
11.6
9.5
8.2
6.8
6.1
5.4
4
5
17.5
14.9
12.3
10.5
8.8
7.9
7
5.5
7.5
22
18.7
15.4
13.2
11
9.9
8.8
7.5
10
28
23.8
19.6
16.8
14
12.6
11.2
11
15
42
35.7
29.4
25.2
21
18.9
16.8
15
20
54
45.9
37.8
32.4
27
24.3
21.6
18.5
25
68
57.8
47.6
40.8
34
30.6
27.2
22
30
80
68
56
48
40
36
32
30
40
104
88.4
72.8
62.4
52
46.8
41.6
37
50
130
110.5
91
–
–
–
–
45
60
154
130.9
107.8
–
–
–
–
55
75
178
151.3
124.6
–
–
–
–
Rated power
1)
at 50 Hz 400 V 3 AC
Rated output current in A
for a pulse frequency of
kW
hp
2 kHz
4 kHz
6 kHz
8 kHz
10 kHz
12 kHz
14 kHz
16 kHz
0.55
0.75
1.7
1.7
1.45
1.19
1.02
0.85
0.77
0.68
0.75
1
2.2
2.2
1.87
1.54
1.32
1.1
0.99
0.88
1.1
1.5
3.1
3.1
2.64
2.17
1.86
1.55
1.4
1.24
1.5
2
4.1
4.1
3.49
2.87
2.46
2.05
1.85
1.64
2.2
3
5.9
5.9
5.02
4.13
3.54
2.95
2.66
2.36
3
4
7.7
7.7
6.55
5.39
4.62
3.85
3.47
3.08
4
5
10.2
10.2
8.7
7.1
6.1
5.1
4.6
4.1
5.5
7.5
13.2
13.2
11.2
9.2
7.9
6.6
5.9
5.3
7.5
10
18
18
15.3
12.6
10.8
9
8.1
7.2
11
15
26
26
22.1
18.2
15.6
13
11.7
10.4
15
20
32
32
27.2
22.4
19.2
16
14.4
12.8
18.5
25
38
38
32.3
26.6
22.8
19
17.1
15.2
22
30
45
45
38.3
31.5
27
22.5
20.3
18
30
40
60
60
51
42
36
30
27
24
37
50
75
75
63.8
52.5
45
37.5
33.8
30
45
60
90
90
76.5
63
54
45
40.5
36
55
75
110
110
93.5
77
66
55
49.5
44
75
100
145
145
123.25
108.75
–
–
–
–
90
125
178
178
151.3
133.5
–
–
–
–
110
150
205
205
–
–
–
–
–
–
132
200
250
250
–
–
–
–
–
–
1)
Rated power based on the rated output current
I
rated
. The rated output
current
I
rated
is based on the duty cycle for low overload (LO).
© Siemens AG 2016