SIEMENS
5/92
Siemens D 31 N · March 2016
SINAMICS G120 standard inverters
0.37 kW to 250 kW (0.5 hp to 400 hp)
Line-side components
> Recommended line-side power components
5
■
Selection and ordering data
The following tables list recommendations for additional line-
side components, such as fuses and circuit breakers. The
values in the table take into account the overload capability of
the inverter.
Notes
for use in compliance with IEC standards:
3NA3 or 3NE1 fuses and 3RV motor starter protectors or 3VL
circuit breakers are recommended for European countries.
Notes
for use in compliance with UL regulations:
UL-listed fuses Class J, T, CC, G or CF (with rated voltage
250 V AC or 600 V AC) or 3NE1 (UL-compliant – corresponds to
U
) are required for North America.
Short Circuit Current Rating (SCCR)
according to UL
Applies to industrial control panel installations to
NEC Article 409 or UL 508A/508C
•
PM230: 65 kA (variants with IP20 degree of protection)
•
PM240-2: 100 kA (200 V versions), 100 kA (400 V versions),
65 kA (690 V versions)
(the value depends on the fuses and circuit breakers used)
•
PM240: 65 kA
•
PM250: 40 kA (frame size FSC), 42 kA (frame sizes FSD to
FSF)
Notes
regarding installations in Canada:
Overvoltage protection devices in accordance with overvoltage
category III and with the following ratings must be connected on
the line side of the inverter:
•
Rated voltage 480 V (phase-phase) and 480 V (phase-
ground)
•
Voltage limit 4 kV (phase-phase) and 6 kV (phase-ground)
All overvoltage protection devices used must comply with
Canadian standards for industrial installations.
Further information, particularly regarding use in accordance
with UL guidelines, is available at
Additional information about the line-side power components
can be found in Catalogs LV 10, IC 10 and IC 10 AO as well as
the Industry Mall.
Rated power
1)
PM230
Power Module
degree of protection IP20
standard variant
IEC-compliant
UL/cUL-compliant
Fuse
Fuse
Fuse type
Rated voltage
600 V AC
Type
Current
Type 3NE1 (
U
)
Type 3NE1 (
U
)
Current
kW
hp
6SL3210-...
Frame size
A
Article No.
Article No.
Class
A
380 ... 480 V 3 AC
0.37
0.5
1NE11-3 . L1
FSA
16
3NE1813-0
3NE1813-0
J
15
0.55
0.75
1NE11-7 . L1
FSA
16
3NE1813-0
3NE1813-0
J
15
0.75
1
1NE12-2 . L1
FSA
16
3NE1813-0
3NE1813-0
J
15
1.1
1.5
1NE13-1 . L1
FSA
16
3NE1813-0
3NE1813-0
J
15
1.5
2
1NE14-1 . L1
FSA
16
3NE1813-0
3NE1813-0
J
15
2.2
3
1NE15-8 . L1
FSA
16
3NE1813-0
3NE1813-0
J
15
3
4
1NE17-7 . L1
FSA
16
3NE1813-0
3NE1813-0
J
15
4
5
1NE21-0 . L1
FSB
25
3NE1815-0
3NE1815-0
J
25
5.5
7.5
1NE21-3 . L1
FSB
25
3NE1815-0
3NE1815-0
J
25
7.5
10
1NE21-8 . L1
FSB
25
3NE1815-0
3NE1815-0
J
25
11
15
1NE22-6 . L1
FSC
50
3NE1817-0
3NE1817-0
J
50
15
20
1NE23-2 . L1
FSC
50
3NE1817-0
3NE1817-0
J
50
18.5
25
1NE23-8 . L1
FSC
50
3NE1817-0
3NE1817-0
J
50
22
30
1NE24-5 . L0
FSD
63
3NE1818-0
3NE1818-0
–
–
30
40
1NE26-0 . L0
FSD
80
3NE1820-0
3NE1820-0
–
–
37
50
1NE27-5 . L0
FSE
100
3NE1021-0
3NE1021-0
–
–
45
60
1NE28-8 . L0
FSE
125
3NE1022-0
3NE1022-0
–
–
55
75
1NE31-1 . L0
FSF
160
3NE1224-0
3NE1224-0
–
–
75
100
1NE31-5 . L0
FSF
200
3NE1225-0
3NE1225-0
–
–
1)
Rated power based on the rated output current
I
rated
. The rated
output current
I
rated
is based on the duty cycle for low overload (LO).
© Siemens AG 2016