SIEMENS
5/48
Siemens D 31 N · March 2016
SINAMICS G120 standard inverters
0.37 kW to 250 kW (0.5 hp to 400 hp)
Power Modules
5
■
Selection and ordering data
To ensure that a suitable Power Module is selected, the following
currents should be used for applications:
•
Rated output current for applications with low overload (LO)
•
Base-load current for applications with high overload (HO)
With reference to the rated output current, the modules
support at least 2-pole to 6-pole low-voltage motors, e.g. the
SIMOTICS 1LE1 motor series. The rated power is merely a
guide value. For a description of the overload performance,
please refer to the general technical specifications of the
Power Modules.
PM230 Power Modules degree of protection IP20 standard variant
PM230 Power Modules degree of protection IP20 push-through variant
Note:
PM230 Power Modules with integrated filter class A or class B,
degree of protection IP55/UL Type 12, 0.37 kW to 90 kW (0.5 to
125 hp) are integral components of the SINAMICS G120P for
pumps, fans and compressors.
Detailed information can be
found in Catalog D 35
.
Rated power
1)
Rated out-
put current
I
rated
2)
Power based
on the base-load
current
3)
Base-load
current
I
H
3)
Frame size
PM230 Power Module
degree of protection IP20
standard variant
without
integrated line filter
PM230 Power Module
degree of protection IP20
standard variant
with
integrated line filter
class A
kW
hp
A
kW
hp
A
Article No.
Article No.
380 ... 480 V 3 AC
0.37
0.5
1.3
0.25
0.33
0.9
FSA
6SL3210-1NE11-3UL1
6SL3210-1NE11-3AL1
0.55
0.75
1.7
0.37
0.5
1.3
FSA
6SL3210-1NE11-7UL1
6SL3210-1NE11-7AL1
0.75
1
2.2
0.55
0.75
1.7
FSA
6SL3210-1NE12-2UL1
6SL3210-1NE12-2AL1
1.1
1.5
3.1
0.75
1
2.2
FSA
6SL3210-1NE13-1UL1
6SL3210-1NE13-1AL1
1.5
2
4.1
1.1
1.5
3.1
FSA
6SL3210-1NE14-1UL1
6SL3210-1NE14-1AL1
2.2
3
5.9
1.5
2
4.1
FSA
6SL3210-1NE15-8UL1
6SL3210-1NE15-8AL1
3
4
7.7
2.2
3
5.9
FSA
6SL3210-1NE17-7UL1
6SL3210-1NE17-7AL1
4
5
10.2
3
4
7.7
FSB
6SL3210-1NE21-0UL1
6SL3210-1NE21-0AL1
5.5
7.5
13.2
4
5
10.2
FSB
6SL3210-1NE21-3UL1
6SL3210-1NE21-3AL1
7.5
10
18
5.5
7.5
13.2
FSB
6SL3210-1NE21-8UL1
6SL3210-1NE21-8AL1
11
15
26
7.5
10
18
FSC
6SL3210-1NE22-6UL1
6SL3210-1NE22-6AL1
15
20
32
11
15
26
FSC
6SL3210-1NE23-2UL1
6SL3210-1NE23-2AL1
18.5
25
38
15
20
32
FSC
6SL3210-1NE23-8UL1
6SL3210-1NE23-8AL1
22
30
45
18.5
25
38
FSD
6SL3210-1NE24-5UL0
6SL3210-1NE24-5AL0
30
40
60
22
30
45
FSD
6SL3210-1NE26-0UL0
6SL3210-1NE26-0AL0
37
50
75
30
40
60
FSE
6SL3210-1NE27-5UL0
6SL3210-1NE27-5AL0
45
60
90
37
50
75
FSE
6SL3210-1NE28-8UL0
6SL3210-1NE28-8AL0
55
75
110
45
60
90
FSF
6SL3210-1NE31-1UL0
6SL3210-1NE31-1AL0
75
100
145
55
75
110
FSF
6SL3210-1NE31-5UL0
6SL3210-1NE31-5AL0
Rated power
1)
Rated out-
put current
I
rated
2)
Power based
on the base-load
current
3)
Base-load
current
I
H
3)
Frame size
PM230 Power Module
degree of protection IP20
push-through variant
without
integrated line filter
PM230 Power Module
degree of protection IP20
push-through variant
with
integrated line filter
class A
kW
hp
A
kW
hp
A
Article No.
Article No.
380 ... 480 V 3 AC
3
4
7.7
2.2
3
5.9
FSA
6SL3211-1NE17-7UL1
6SL3211-1NE17-7AL1
7.5
10
18
5.5
7.5
13.2
FSB
6SL3211-1NE21-8UL1
6SL3211-1NE21-8AL1
18.5
25
38
15
20
32
FSC
6SL3211-1NE23-8UL1
6SL3211-1NE23-8AL1
1)
Rated power based on the rated output current
I
rated
. The rated output
current
I
rated
is based on the duty cycle for low overload (LO).
2)
The rated output current
I
rated
is based on the duty cycle for low overload
(LO). These current values are valid for 400 V and are specified on the
rating plate of the Power Module.
3)
The base-load current
I
H
is based on the duty cycle for high overload
(HO).
© Siemens AG 2016