SIEMENS
5/46
Siemens D 31 N · March 2016
SINAMICS G120 standard inverters
0.37 kW to 250 kW (0.5 hp to 400 hp)
Power Modules
5
■
Integration
Maximum permissible cable lengths from the motor to the inverter when using output reactors or filters depending on the
voltage range and the Power Module being used
The following load-side power components in the appropriate frame sizes are optionally available for the Power Modules and result
in the following maximum cable lengths:
Maximum permissible motor cable lengths (shielded/unshielded) in m (ft)
Frame size
FSA
FSB
FSC
FSD
FSE
FSF
FSGX
PM230 Power Module degree of protection IP20
Available frame sizes
–
With optional output reactor
• At 380 ... 415 V 3 AC
150/225
(492/738)
150/225
(492/738)
150/225
(492/738)
–
–
–
–
• At 440 ... 480 V 3 AC
100/150
(328/492)
100/150
(328/492)
100/150
(328/492)
–
–
–
–
• At 380 ... 480 V 3 AC
–
–
–
200/300
(656/984)
200/300
(656/984)
200/300
(656/984)
–
With optional sine-wave filter
• At 380 ... 480 V 3 AC
–
–
–
200/300
(656/984)
200/300
(656/984)
200/300
(656/984)
–
With integrated line filter class A
(for compliance with EMC category C3)
• At 380 ... 480 V 3 AC
50/- (164/-)
50/- (164/-)
50/- (164/-)
50/- (164/-)
50/- (164/-)
50/- (164/-)
–
With optional external line filter class B
(for compliance with EMC category C1
1)
,
with unfiltered Power Module, maintains
the limit values acc. to EN 61800-3)
• At 380 ... 480 V 3 AC
50/- (164/-)
50/- (164/-)
50/- (164/-)
50/- (164/-)
50/- (164/-)
50/- (164/-)
–
With optional external line filter class B
and output reactor (for compliance
with EMC category C2
1)
, with unfiltered
Power Module, maintains the limit values
acc. to EN 61800-3)
• At 380 ... 415 V 3 AC
150/- (492/-)
150/- (492/-)
150/- (492/-)
–
–
–
–
• At 440 ... 480 V 3 AC
100/- (328/-)
100/- (328/-)
100/- (328/-)
–
–
–
–
PM240-2 Power Module with integrated braking chopper
Available frame sizes
• 200 V versions
–
• 400 V versions
–
• 690 V versions
–
–
–
–
With optional output reactor
• At 200 ... 240 V 1 AC/3 AC
150/225
(492/738)
150/225
(492/738)
150/225
(492/738)
–
–
–
–
• At 380 ... 415 V 3 AC
150/225
(492/738)
150/225
(492/738)
150/225
(492/738)
–
–
–
–
• At 440 ... 480 V 3 AC
100/150
(328/492)
100/150
(328/492)
100/150
(328/492)
–
–
–
–
1)
Further information is available on the Internet at
/sinamics-g120/documentation