SIEMENS
5/72
Siemens D 31 N · March 2016
SINAMICS G120 standard inverters
0.37 kW to 250 kW (0.5 hp to 400 hp)
Power Modules
5
■
Technical specifications
PM250 Power Modules
Line voltage 380 ... 480 V 3 AC
PM250 Power Modules
With integrated line filter
6SL3225-0BE25-5AA1
6SL3225-0BE27-5AA1
6SL3225-0BE31-1AA1
Output current
at 50 Hz 400 V 3 AC
• Rated current
I
rated
1)
A
18
25
32
• Base-load current
I
L
1)
A
18
25
32
• Base-load current
I
H
2)
A
13.2
19
26
• Maximum current
I
max
A
26.4
38
52
Rated power
• Based on
I
L
kW (hp)
7.5 (10)
11 (15)
15 (20)
• Based on
I
H
kW (hp)
5.5 (7.5)
7.5 (10)
11 (15)
Rated pulse frequency
kHz
4
4
4
Efficiency
η
0.95
0.95
0.95
Power loss
3)
At rated current
kW
0.298
0.488
0.472
Cooling air requirement
m
3
/s (ft
3
/s)
0.038 (1.3)
0.038 (1.3)
0.038 (1.3)
Sound pressure level
L
pA
(1 m)
dB
<60
<60
<60
24 V DC power supply
for Control Unit
A
1
1
1
Input current
4)
• Rated current
A
18
25
32
• Based on
I
H
A
13.2
19
26
Line supply connection
U1/L1, V1/L2, W1/L3
Screw terminals
Screw terminals
Screw terminals
• Conductor cross-section
mm
2
2.5 ... 10
2.5 ... 10
2.5 ... 10
Motor connection
U2, V2, W2
Screw terminals
Screw terminals
Screw terminals
• Conductor cross-section
mm
2
2.5 ... 10
2.5 ... 10
2.5 ... 10
PE connection
On housing with M5 screw
On housing with M5 screw
On housing with M5 screw
Motor cable length, max.
• Shielded
m (ft)
25 (82)
25 (82)
25 (82)
• Unshielded
m (ft)
100 (328)
100 (328)
100 (328)
Degree of protection
IP20
IP20
IP20
Dimensions
• Width
mm (in)
189 (7.44)
189 (7.44)
189 (7.44)
• Height
mm (in)
334 (13.15)
334 (13.15)
334 (13.15)
• Depth
-
Without operator panel
mm (in)
185 (7.28)
185 (7.28)
185 (7.28)
-
With operator panel, max.
mm (in)
268 (10.55)
268 (10.55)
268 (10.55)
Frame size
FSC
FSC
FSC
Weight, approx.
kg (lb)
7.5 (16.5)
7.5 (16.5)
7.5 (16.5)
1)
The rated output current
I
rated
and the base-load current
I
L
are based on
the duty cycle for low overload (LO).
2)
The base-load current
I
H
is based on the duty cycle for high overload
(HO).
3)
Typical values. You can find additional information on the Internet at
4)
The input current depends on the motor load and line impedance and
applies for a line impedance corresponding to
u
K
= 1 %. The rated input
currents apply for a load at rated power (based on
I
rated
) – these current
values are specified on the rating plate.
© Siemens AG 2016