SIEMENS
5/70
Siemens D 31 N · March 2016
SINAMICS G120 standard inverters
0.37 kW to 250 kW (0.5 hp to 400 hp)
Power Modules
5
■
Technical specifications
Line voltage 380 ... 480 V 3 AC
PM240-2 Power Modules push-through variant
Without integrated line filter
6SL3211-1PE18-0UL1
6SL3211-1PE21-8UL0
6SL3211-1PE23-3UL0
With integrated line filter class A
6SL3211-1PE18-0AL1
6SL3211-1PE21-8AL0
6SL3211-1PE23-3AL0
Output current
at 50 Hz 400 V 3 AC
• Rated current
I
rated
1)
A
7.7
18
32
• Base-load current
I
L
1)
A
7.7
18
32
• Base-load current
I
H
2)
A
5.9
13.2
26
• Maximum current
I
max
A
11.8
27
52
Rated power
• Based on
I
L
kW (hp)
3 (4)
7.5 (10)
15 (20)
• Based on
I
H
kW
2.2 (3)
5.5 (7.5)
11 (15)
Rated pulse frequency
kHz
4
4
4
Efficiency
η
>96
>97
>97
Power loss
3)
At rated current
kW
0.113
0.239
0.385
Cooling air requirement
m
3
/s (ft
3
/s)
0.007 (0.2)
0.0092 (0.325)
0.0185 (0.65)
Sound pressure level
L
pA
(1 m)
dB
<56
<62
<65
24 V DC power supply
for Control Unit
A
1
1
1
Input current
4)
• Rated current
A
10.1
22.2
39.9
• Based on
I
H
A
8.8
19.8
36
Line supply connection
U1/L1, V1/L2, W1/L3
Screw terminals, plug-in
Screw terminals, plug-in
Screw terminals, plug-in
• Conductor cross-section
mm
2
1.5 ... 2.5
1.5 ... 6
6 ... 16
Motor connection
U2, V2, W2
Screw terminals, plug-in
Screw terminals, plug-in
Screw terminals, plug-in
• Conductor cross-section
mm
2
1.5 ... 2.5
1.5 ... 6
6 ... 16
Motor cable length, max.
• Without filter,
shielded/unshielded
m (ft)
150/150 (492/492)
150/150 (492/492)
150/150 (492/492)
• With integrated filter class A,
shielded/unshielded
m (ft)
50/100 (164/328)
100/100 (328/328)
5)
150/150 (492/492)
5)
Degree of protection
IP20
IP20
IP20
Dimensions
• Width
mm (in)
126 (4.96)
154 (6.06)
200 (7.87)
• Height
mm (in)
238 (9.37)
345 (13.58)
411 (16.18)
• Depth
-
Without operator panel
mm (in)
171 (6.73)
171 (6.73)
171 (6.73)
-
With operator panel, max.
mm (in)
254 (10.00)
254 (10.00)
254 (10.00)
Frame size
FSA
FSB
FSC
Weight, approx.
With integrated line filter
• Without integrated line filter
kg (lb)
1.7 (3.75)
3.6 (7.94)
5.8 (12.8)
• With integrated line filter
kg (lb)
1.8 (3.97)
3.9 (8.60)
6.3 (13.9)
1)
The rated output current
I
rated
and the base-load current
I
L
are based on
the duty cycle for low overload (LO).
2)
The base-load current
I
H
is based on the duty cycle for high overload
(HO).
3)
Typical values. You can find additional information on the Internet at
4)
The input current depends on the motor load and line impedance and
applies for a line impedance corresponding to
u
K
= 1 %. The rated input
currents apply for a load at rated power (based on
I
rated
) – these current
values are specified on the rating plate.
5)
The values apply with low-capacitance CY cables - the max. permissible
motor cable length is 50 m (164 ft) (shielded) as standard.
© Siemens AG 2016