SIEMENS
5/63
Siemens D 31 N · March 2016
SINAMICS G120 standard inverters
0.37 kW to 250 kW (0.5 hp to 400 hp)
Power Modules
5
■
Technical specifications
Line voltage 380 ... 480 V 3 AC
PM240-2 Power Modules standard variant
Without integrated line filter
6SL3210-
1PE11-8UL1
6SL3210-
1PE12-3UL1
6SL3210-
1PE13-2UL1
6SL3210-
1PE14-3UL1
6SL3210-
1PE16-1UL1
6SL3210-
1PE18-0UL1
With integrated line filter class A
6SL3210-
1PE11-8AL1
6SL3210-
1PE12-3AL1
6SL3210-
1PE13-2AL1
6SL3210-
1PE14-3AL1
6SL3210-
1PE16-1AL1
6SL3210-
1PE18-0AL1
Output current
at 50 Hz 400 V 3 AC
• Rated current
I
rated
1)
A
1.7
2.2
3.1
4.1
5.9
7.7
• Base-load current
I
L
1)
A
1.7
2.2
3.1
4.1
5.9
7.7
• Base-load current
I
H
2)
A
1.3
1.7
2.2
3.1
4.1
5.9
• Maximum current
I
max
A
2.6
3.4
4.7
6.2
8.9
11.8
Rated power
• Based on
I
L
kW (hp)
0.55 (0.75)
0.75 (1)
1.1 (1.5)
1.5 (2)
2.2 (3)
3 (4)
• Based on
I
H
kW (hp)
0.37 (0.5)
0.55 (0.75)
0.75 (1)
1.1 (1.5)
1.5 (2)
2.2 (3)
Rated pulse frequency
kHz
4
4
4
4
4
4
Efficiency
η
>0.96
>0.96
>0.96
>0.96
>0.96
>0.96
Power loss
3)
At rated current
kW
0.033
0.038
0.048
0.061
0.085
0.113
Cooling air requirement
m
3
/s (ft
3
/s)
0.005 (0.18)
0.005 (0.18)
0.005 (0.18)
0.005 (0.18)
0.005 (0.18)
0.005 (0.18)
Sound pressure level
L
pA
(1 m)
dB
<50
<50
<50
<50
<50
<50
24 V DC power supply
for Control Unit
A
1
1
1
1
1
1
Input current
4)
• Rated current
A
2.3
2.9
4.1
5.5
7.7
10.1
• Based on
I
H
A
2
2.6
3.3
4.7
6.1
8.8
Line supply connection
U1/L1, V1/L2, W1/L3
Terminal
connector
Terminal
connector
Terminal
connector
Terminal
connector
Terminal
connector
Terminal
connector
• Conductor cross-section
mm
2
1 ... 2.5
1 ... 2.5
1 ... 2.5
1 ... 2.5
1 ... 2.5
1 ... 2.5
Motor connection
U2, V2, W2
Terminal
connector
Terminal
connector
Terminal
connector
Terminal
connector
Terminal
connector
Terminal
connector
• Conductor cross-section
mm
2
1 ... 2.5
1 ... 2.5
1 ... 2.5
1 ... 2.5
1 ... 2.5
1 ... 2.5
PE connection
Included in
terminal
connector
Included in
terminal
connector
Included in
terminal
connector
Included in
terminal
connector
Included in
terminal
connector
Included in
terminal
connector
Motor cable length, max.
• Without filter,
shielded/unshielded
m (ft)
150/150
(492/492)
150/150
(492/492)
150/150
(492/492)
150/150
(492/492)
150/150
(492/492)
150/150
(492/492)
• With integrated filter class A,
shielded/unshielded
m (ft)
50/100
(164/328)
50/100
(164/328)
50/100
(164/328)
50/100
(164/328)
50/100
(164/328)
50/100
(164/328)
Degree of protection
IP20
IP20
IP20
IP20
IP20
IP20
Dimensions
• Width
mm (in)
73 (2.87)
73 (2.87)
73 (2.87)
73 (2.87)
73 (2.87)
73 (2.87)
• Height
mm (in)
196 (7.72)
196 (7.72)
196 (7.72)
196 (7.72)
196 (7.72)
196 (7.72)
• Depth
165 (6.50)
165 (6.50)
165 (6.50)
165 (6.50)
165 (6.50)
165 (6.50)
-
Without operator panel
mm (in)
165 (6.50)
165 (6.50)
165 (6.50)
165 (6.50)
165 (6.50)
165 (6.50)
-
With operator panel, max.
mm (in)
248 (9.76)
248 (9.76)
248 (9.76)
248 (9.76)
248 (9.76)
248 (9.76)
Frame size
FSA
FSA
FSA
FSA
FSA
FSA
Weight, approx.
• Without integrated line filter
kg (lb)
1.4 (3.09)
1.4 (3.09)
1.4 (3.09)
1.4 (3.09)
1.4 (3.09)
1.4 (3.09)
• With integrated line filter
kg (lb)
1.5 (3.31)
1.5 (3.31)
1.5 (3.31)
1.5 (3.31)
1.5 (3.31)
1.5 (3.31)
1)
The rated output current
I
rated
and the base-load current
I
L
are based on
the duty cycle for low overload (LO).
2)
The base-load current
I
H
is based on the duty cycle for high overload
(HO).
3)
Typical values. You can find additional information on the Internet at
4)
The input current depends on the motor load and line impedance. The
input currents apply for a load at rated power (based on
I
rated
) for a line
impedance corresponding to
u
K
= 1 %. The current values are specified
on the rating plate of the Power Module.
© Siemens AG 2016