SIEMENS
SINAMICS GM150
Medium-Voltage Converter
SINAMICS GM150 in IGBT version
2/19
Siemens D 12 · 2012
2
■
Technical specifications
Note:
The values specified under storage and transport apply to
suitably packed converters.
Operation of induction motors
Operation of separately excited
synchronous motors
Without speed encoder
With speed encoder
With speed encoder
Without
sine-wave filter
With
sine-wave filter
Without
sine-wave filter
With
sine-wave filter
Without
sine-wave filter
With
sine-wave filter
Control properties
Operating range
• Lower limit of speed control range
(% of rated motor speed)
5 %
5 %
0 %
0 %
0 %
0 %
• Max. permissible output
frequency
250 Hz
66 Hz
250 Hz
66 Hz
90 Hz
66 Hz
• Field-shunting range
1:3
1:1.1
1:3
1:1.1
1:4
1:1.1
Stationary operation
• Speed accuracy
(% of rated motor speed)
±0.2 %
(from 5 %
of rated speed)
±0.2 %
(from 5 %
of rated speed)
±0.01 %
±0.01 %
±0.01 %
±0.01 %
• Torque accuracy
(% of rated torque)
±5 %
(from 5 %
of rated speed)
±5 %
(from 5 %
of rated speed)
±5 %
±5 %
±2 %
±5 %
Dynamic operation
• Torque rise time
5 ms
20 ms
5 ms
20 ms
5 ms
20 ms
Storage
Transport
Operation
Climatic ambient conditions
Ambient temperature
-25 ... +70 °C
-25 ... +70 °C
5 ... 40 °C (air cooling)
5 ... 45 °C (water cooling)
Relative air humidity
5 ... 95 %
(only slight condensation permitted;
converter must be completely dry
before commissioning)
5 ... 75 %
5 ... 85 %
(condensation not permissible)
Other climatic conditions
in accordance with Class
1K3 according to EN 60721-3-1
(IEC 60721-3-1)
(icing not permitted)
2K2 according to EN 60721-3-2
(IEC 60721-3-2)
3K3 according to EN 60721-3-3
(IEC 60721-3-3)
Degree of pollution
2 without conductive pollution
according to EN 50178/VDE 0160
(IEC 62103)
2 without conductive pollution
according to EN 50178/VDE 0160
(IEC 62103)
2 without conductive pollution
according to EN 50178/VDE 0160
(IEC 62103)
Mechanical ambient conditions
Dynamic stress
• Deflection
1.5 mm at 2 ... 9 Hz
3.5 mm at 2 ... 9 Hz
0.3 mm at 2 ... 9 Hz
• Acceleration
5 m/s
2
at 9 ... 200 Hz
10 m/s
2
at 9 ... 200 Hz
15 m/s
2
at 200 ... 500 Hz
1 m/s
2
at 9 ... 200 Hz
Other mechanical conditions in
accordance with Class
(increased strength for marine duty)
1M2 according to EN 60721-3-1
(IEC 60721-3-1)
2M2 according to EN 60721-3-2
(IEC 60721-3-2)
3M1 according to EN 60721-3-3
(IEC 60721-3-3)
Other ambient conditions
Biological ambient conditions
in accordance with Class
1B1 according to EN 60721-3-1
(IEC 60721-3-1)
2B1 according to EN 60721-32-
(IEC 60721-3-2)
3B2 according to EN 60721-3-3
(IEC 60721-3-3)
(without harmful flora)
Chemically active substances
in accordance with Class
1C1 according to EN 60721-3-1
(IEC 60721-3-1)
2C1 according to EN 60721-3-2
(IEC 60721-3-2)
3C2 according to EN 60721-3-3
(IEC 60721-3-3)
(no occurrence of salt mist)
Mechanically active substances
in accordance with Class
1S1 according to EN 60721-3-1
(IEC 60721-3-1)
2S1 according to EN 60721-3-2
(IEC 60721-3-2)
3S1 according to EN 60721-3-3
(IEC 60721-3-3)
(3S3 with water cooling and degree
of protection IP54)
© Siemens AG 2012