SIEMENS
9
Permissible cable lengths
01/28/2015
© Siemens AG 2015
34
SINAMICS GM150 SINAMICS SM150
Supplement for Catalog D 12 2012
9
Permissible cable lengths
9.1
With and without output reactor or dv/dt filter
The following table shows an update of the specifications of permissible cable
lengths with and without output reactor (catalog page 9/14). In addition, the table
includes specifications for operation with and without dv/dt filter.
Note
The option L08 (output reactor) is only available for SINAMICS GM150 and
SINAMICS SM150 in
IGBT
version.
The option L10 (dv/dt filter) is only available for SINAMICS GM150 and
SINAMICS SM150 in
IGCT
version.
Table 3-1
Maximum cable length
Without output reactor (standard)
With output reactor (option
L08
)
1)
SINAMICS GM150 IGBT version and SINAMICS SM150 IGBT version
Output voltage 2.3 kV
Up to 2 parallel cables: each 100 m
3 parallel cables: each 80 m
4 parallel cables: each 80 m
Up to 4 cables in parallel: 1000 m
Output voltage 3.3 kV
Up to 4 cables in parallel: 1000 m
Output voltage 4.16 kV
•
Up to 2 cables in parallel: 1000 m
•
3 to 4 cables in parallel: 350 m
(longer lengths on request)
Mechanically, up to six parallel cables are possible (on request).
Without dv/dt filter (standard)
With dv/dt filter (option
L10
)
1)
SINAMICS GM150 IGCT version and SINAMICS SM150 IGCT version
Output voltage 3.3 kV
Up to 2 parallel cables: each 100 m
3 parall cables: each 80 m
4 parall cables: each 80 m
200m
Larger cable lengths on request
Mechanically, up to six parallel cables are possible (on request).
1) Distance converter-motor depending on the current load for max. four shielded three-wire cables in
parallel (when using single-core cables, refer to catalog page 9/13) – unshielded cables are not
permitted