7.3.4
M11
Dust protection (air-cooled converters)
The description of option M11 has to be supplemented as follows.
Note
To protect the converter if high levels of dust are present, it is recommended to
order option M11 for steel, rolling mill and cement plant applications.
7.3.5
M16
Extended dust protection (SINAMICS GM150 in water-cooled
IGBT versions)
The description of option M16 has to be supplemented as follows.
Note
When selecting option M66 (suitable for marine duty), we recommend that option
M16 is simultaneously ordered.
7.3.6
N15
24-pulse Basic Line Module
The description of option N15 has to be supplemented as follows.
Note
With option N15 the deionized water requirement of the cooling unit is 6 l higher
than that specified in the technical data.
7.3.7
M36
Brass cable entry for power cables
(SINAMICS GM150, SINAMICS SM150 in the IGCT version)
The description of option M36 has to be supplemented as follows.
Note
1.5 mm thick brass plate is used for the cable entry.