Engineering information
SINAMICS GM150, SINAMICS SM150
Scope of delivery
9/17
Siemens D 12 · 2012
9
■
Configuration
The standard scope of delivery of the SINAMICS GM150 and
SINAMICS SM150 comprises:
1. Basic unit
The basic unit consists of the converter power unit including
closed-loop control, in either an air-cooled or water-cooled ver-
sion. One or more transport units are supplied depending on the
converter type. Exact details are to be found in the dimension
drawing for the specific order.
SINAMICS SM150 includes a VSM10 Voltage Sensing Module in
the basic unit. The VSM10 detects the line supply voltage re-
garding phase position, frequency and amplitude. A voltage
transformer, which should be provided on the primary side of the
circuit breaker (plant-side) is used for this purpose.
2. Cooling unit for water-cooled converters
The cooling unit consists of one transport unit and is supplied
without deionized water.
For SINAMICS GM150 in the IGBT version, a pipe-connecting
element between the cooling unit and converter is included in
the scope of delivery.
For SINAMICS GM150 in the IGCT version and
SINAMICS SM150 in the IGCT version, the piping between the
cooling unit and the basic unit is routed below the units. The
necessary pipes and connection pieces are included in the
scope of delivery and are supplied loose.
Special installation conditions have not been taken into account
and, where applicable, a separate inquiry is necessary (e.g.
where the cooling unit is not mounted directly next to the basic
unit).
The piping for the raw water supply on the plant side is not
included.
3. Optional components
Optional components, e.g. sine-wave filters or output reactors,
are delivered as separate transport units. If necessary, cables
for connecting the optional components to the power unit are
delivered as well. For the DC bus configurations of
SINAMICS SM150, the cabling between the basic unit and the
option cabinets is routed below the units. The cables required
are not included in the scope of delivery as they have to be
selected according to the particular project.
4. Static excitation unit
A static excitation unit is generally included in the scope of
delivery for converters to supply synchronous motors. This must
be ordered with a separate order number
(see Accessories,
Chapter 7)
.
The following items are not included in the standard scope
of delivery:
•
Cables between the transformer and the converter
•
Motor cables
•
Circuit breakers
•
Transformer
•
Motor
•
Cable ducts
•
Filter systems
•
Piping for the raw water circuit of the cooling unit
•
Voltage transformer for the synchronizing voltage of the
VSM10
•
Basic configuration for SINAMICS SM150
Basic configuration for SINAMICS SM150
For the SINAMICS SM150 converter system, it is absolutely
necessary
that the software is configured for the specific plant
or system.
This involves:
•
connection of the static excitation unit via PROFIBUS
•
operation of the SIMATIC OP 177B operator panel
•
signal marshaling to connect to the basic automation (e.g.
ON/OFF or fault signals from Motor Modules)
Without this basic configuration, the SINAMICS SM150 con-
verter system cannot function. The basic configuration should
either be undertaken by a system integrator or option
S05
should be ordered.
Beyond this, in individual cases, application-specific engineer-
ing is required, which is not emulated in the product, but can be
implemented in coordination with the system integrator.
This includes:
•
power pre-control of several Motor Modules on a common
infeed
•
power monitoring
•
control of auxiliaries with temperature/flow/bearings
•
communication configuration to the PDA (Process Data
Acquisition) via PROFINET
•
integration of additional options