Engineering information
SINAMICS GM150, SINAMICS SM150
Power cables
9/14
Siemens D 12 · 2012
9
■
Configuration
Permissible cable lengths
In the case of long cables between the converter and the motor,
reflection phenomena lead to overvoltages and recharging
currents on the cables and at the motor terminals and, in turn, to
a higher level of stress on the motor insulation. The motor insula-
tion is additionally subject to stress as a result of the voltage
rates of rise (voltage gradients).
The increased stress on the cables and motor as a result of
reflection phenomena in the case of long cables can be signifi-
cantly reduced using a sine-wave filter at the converter output
(option
Y15
).
The recharging currents in the cables and in the motor can be
significantly reduced by using reactors at the converter output
(option
L08
).
Maximum cable lengths without and with output reactor
Data regarding cable lengths when using option
L08
(output reactor) can be obtained for specific systems from
your local Siemens sales contact.
Maximum cable lengths without and with sine-wave filter
Maximum cable lengths between line-side transformer
and converter
Converter
Max. cable lengths
Without
output reactor
(standard)
With
output reactor
1)
(option
L08
)
Shielded
Un-
shielded
Shielded
Un-
shielded
Output voltage 2.3 kV to 4.16 kV
SINAMICS GM150
IGBT version and
SINAMICS SM150
IGBT version
Up to
2 parallel
cables:
each 100 m
3 parallel
cables:
each 80 m
>3 parallel
cables:
Not permitted
Not per-
mitted
On request
Not per-
mitted
Output voltage 3.3 kV
SINAMICS GM150
as IGCT version
Up to
2 parallel
cables:
each 100 m
3 parallel
cables:
each 80 m
4 parallel
cables:
each 80 m
Not per-
mitted
On request
Not per-
mitted
Mechanically, up to six parallel cables are
possible (on request).
SINAMICS SM150
IGCT version
Up to
4 parallel
cables:
each 80 m
Not per-
mitted
On request
Not per-
mitted
Mechanically, up to six parallel cables are
possible (on request).
Converter
Max. cable lengths
Without
sine-wave filter
(standard)
With
sine-wave filter
1)
(option
Y15
)
Shielded
Un-
shielded
Shielded
Un-
shielded
2)
Output voltage 2.3 kV to 4.16 kV
SINAMICS GM150
in IGBT version
Up to
2 parallel
cables:
each 100 m
3 parallel
cables:
each 80 m
>3 parallel
cables:
Not permitted
Not per-
mitted
1000 m
1000 m
Converter
Max. cable lengths
Shielded
Unshielded
Output voltage 2.3 kV to 4.16 kV
SINAMICS GM150
300 m
300 m
Output voltage 3.3 kV
SINAMICS SM150
80 m
Not permitted
1)
Distance between the converter and the motor depending on the current
load for max. 6 three-wire EMC cables connected in parallel.
2)
Armored cables recommended.