The interfaces of the TM31 and TM15 Terminal Modules are
available for communication with the higher level. Additional
terminal strips can be used to connect the circuit breaker or
external protection and monitoring devices. The following tables
give an overview of the type and preassignment of the interfaces
in the standard version.
Note:
For max. conductor cross-section and further technical
data on TM31 and TM15 Terminal Modules,
see Description of
options
G61
and
G63
, Pages 6/16 and 6/20
.
Terminal strip on TM31 (=.HC–A51)
Terminal
Type
Preassign-
ment
Comment
X540:
1-8
P24
24 V DC supply for
inputs DI0 to DI7
–
–
X520:
1
DI0
Digital input
electrically isolated
via optocoupler
Preassigned
internally
–
2
DI1
Preassigned
internally
–
3
DI2
–
–
4
DI3
–
–
5
M1
Reference ground
for digital inputs
DI0 to DI3
–
–
6
M
Reference ground
for P24, auxiliary
voltage for digital
inputs
–
–
X530:
1
DI4
Digital input
electrically isolated
via optocoupler
Preassigned
internally
–
2
DI5
–
–
3
DI6
–
–
4
DI7
–
–
5
M2
Reference ground
for digital inputs
DI4 to DI7
–
–
6
M
Reference ground
for P24, auxiliary
voltage for digital
inputs
–
–
X541:
1
P24
24 V DC supply
for inputs/outputs
DI/O8 to DI/DO11
–
–
2
DI/DO8
Digital inputs/digital
outputs non-isolated
Preassigned
internally
–
3
DI/DO9
–
–
4
DI/DO10
–
–
5
DI/DO11
–
–
6
M
Reference ground
for P24, ground of
digital inputs/
digital outputs
–
–
Terminal strip on TM31 (=.HC–A51)
Terminal
Type
Preassign-
ment
Comment
X521:
1
AI0+
Analog inputs set
up as differential
inputs for the
following ranges:
-10 ... +10 V
+4 ... +20 mA
0 ... +20 mA
-20 ... +20 mA
The voltage input/
current input is
selected with a
switch
Main
speed
setpoint
Isolating
amplifiers are
used here
for electrical
isolation
(4 ... 20 mA,
0 ... 10 V,
0 ... 20 mA)
2
AI0-
3
AI1+
Additional
speed
setpoint
Isolating
amplifiers
are used here
for electrical
isolation
(4 ... 20 mA,
0 ... 10 V,
0 ... 20 mA)
4
AI1-
5
P10
Auxiliary voltage
± 10 V (10 mA)
to connect a
potentiometer to
enter a setpoint
via an analog input
–
–
6
M
–
–
7
N10
–
–
8
M
–
–
X522:
1
AO 0V+
Analog outputs
for the following
ranges:
-10 ... +10 V
+4 ... +20 mA
0 ... +20 mA
-20 ... +20 mA
Main
actual
value
(speed)
Isolating
amplifiers
are used here
for electrical
isolation
(4 ... 20 mA,
0 ... 10 V,
0 ... 20 mA)
2
AO 0V-
3
AO0C+
4
AO 1V+
Additional
actual
value
(speed)
Isolating
amplifiers
are used here
for electrical
isolation
(4 ... 20 mA,
0 ... 10 V,
0 ... 20 mA)
5
AO 1V-
6
AO 1C+
7
KTY+
Temperature sensor
KTY84 0 ... 200 °C
or PTC
(
R
cold
< 1.5 k
Ω
)
–
The sensor
type must be
parameter-
ized
8
KTY-
–
X542:
1
DO 0.NC
Relay output for
changeover contact
Max. switching
voltage:
250 V AC, 30 V DC
Max. switching
power at 250 V AC:
2000 VA
Max. switching
power at 30 V DC:
240 W
–
NC contact
2
DO 0.COM
–
Basic
3
DO 0.NO
–
NO contact
4
DO 1.NC
Relay output for
changeover contact
Max. switching
voltage:
250 V AC, 30 V DC
Max. switching
power at 250 V AC:
2000 VA
Max. switching
power at 30 V DC:
240 W
–
NC contact
5
DO 1.COM
–
Basic
6
DO 1.NO
–
NO contact
© Siemens AG 2012