SIEMENS
Description of options
SINAMICS GM150, SINAMICS SM150
Description of options
6/40
Siemens D 12 · 2012
6
■
Options
N35 to N38
Controlled outgoing feeder for auxiliaries
230 V 1 AC/120 V 1 AC
A controlled outgoing feeder protected by miniature circuit
breakers is available in the converter for controlling external
auxiliaries, e.g. the anti-condensation heating for the motor. The
infeed required for the voltage supply, e.g. the anti-condensation
heating, must be provided externally.
Depending on the output that is required, four different outgoing
feeders are available.
The contactor is opened with the
ON
command at the converter
and closed with the
OFF
command.
Note:
It is not possible to combine several options (
N35 to N38
).
Q80 to Q85
Extension of the liability for defects
For a description, refer to services and documentation,
Pages 10/12 and 10/13.
S05
Basic configuration (SINAMICS SM150)
Option
S05
provides a system-specific software configuration,
which is absolutely necessary
for the correct functioning of the
SINAMICS SM150 converter system. If option
S05
is not
selected, then a system integrator must carry out this basic
configuration.
The basic configuration includes:
•
Connection of the static excitation unit via PROFIBUS
•
Operation of the SIMATIC OP 177B operator panel
•
Signal marshaling to connect to the basic automation (e.g.
ON/OFF or fault signals from Motor Modules)
T58, T60, T80, T85, T90, T91
Rating plate languages
The rating plate is normally supplied in two languages
(English/German). Other languages can be ordered using
the codes below.
Note:
It is not possible to combine several options (
T58 to T91
).
Option
Description
N35
Controlled outgoing feeder for auxiliaries
50 Hz 230 V 1 AC, max. 1.2 kW or
60 Hz 120 V 1 AC, max. 1 kW
N36
Controlled outgoing feeder for auxiliaries
50 Hz 230 V 1 AC, max. 2.2 kW or
60 Hz 120 V 1 AC, max. 1.5 kW
N37
Controlled outgoing feeder for auxiliaries
50 Hz 230 V 1 AC, max. 3.5 kW or
60 Hz 120 V 1 AC, max. 2.1 kW
N38
Controlled outgoing feeder for auxiliaries
50 Hz 230 V 1 AC, max. 4.5 kW or
60 Hz 120 V 1 AC, max. 2.8 kW
Auxiliary
voltage infeed
Outgoing feeder
for auxiliaries
Protective circuit breaker
external power supply ON
= GC–X1:7 L1
= GC–X1:9 L1
= GC–X2:3
Relay contact,
max. 60 V DC
= GC–X1:8 N
= GC–X1:10 L2
= GC–X2:4
Option
Description
T58
Rating plate in English/French
T60
Rating plate in English/Spanish
T80
Rating plate in English/Italian
T82
Rating plate in English/Portuguese (on request)
T85
Rating plate in English/Russian (on request)
T86
Rating plate in English/Polish (on request)
T90
Rating plate in English/Japanese (on request)
T91
Rating plate in English/Chinese (on request)
© Siemens AG 2012