SIEMENS
Description of options
SINAMICS GM150, SINAMICS SM150
Description of options
6/36
Siemens D 12 · 2012
6
■
Options
M78
Power cables at the converter output are connected
from the top
(SINAMICS GM150 in the IGBT version)
Given suitable installation conditions, option
M78
enables the
motor-side power cable to be introduced into the cabinet unit
from the top.
Option
M78
includes option
M13
(power cable connection at the
converter input from the top).
Notice:
Option
M78
increases the cabinet width by 600 mm. When
simultaneously selecting option
L08
(output reactor) or
Y15
(sine-wave filter) the width does not increase. In the case of
option
Y15
, the dimensions in the Technical specifications apply.
N06 to N08
Capacitor Modules to increase the DC link capacitance
(SINAMICS SM150 in IGCT version)
With options
N06 to N08
the converter is shipped with Capacitor
Modules to increase the DC link capacitance. The increase for
each sub DC link is 6, 12 or 18 mF.
Note:
Options
N06 to N08
are only available for the basic and parallel
connections with order numbers 6SL3845-7NN42-2AA0,
6SL3845-7NN44-5AA0 and 6SL3845-7NN46-7AA0. They are
not available for DC bus configurations.
With these options, the cabinet width per converter unit is
increased (
see the following table
).
Terminal strip on TM31 (=.HC–A71)
Terminal
Type
Preassign-
ment
Comment
X521:
1
AI0+
Analog inputs set
up as differential
inputs for the
following ranges:
-10 ... +10 V
+4 ... +20 mA
0 ... +20 mA
-20 ... +20 mA
The voltage input/
current input is
selected with a
switch
Cooling
unit flow
measure-
ment with
4 ... 20 mA
signal
–
2
AI0-
3
AI1+
–
–
4
AI1-
5
P10
Auxiliary voltage
± 10 V (10 mA) to
connect a poten-
tiometer to enter a
setpoint via an
analog input
–
–
6
M
–
–
7
N10
–
–
8
M
–
–
X522:
1
AO 0V+
Analog outputs
for the following
ranges:
-10 ... +10 V
+4 ... +20 mA
0 ... +20 mA
-20 ... +20 mA
–
–
2
AO 0V-
3
AO0C+
4
AO 1V+
–
–
5
AO 1V-
6
AO 1C+
7
KTY+
Temperature sensor
KTY84 0 ... 200 °C
or PTC
(
R
cold
< 1.5 k
Ω
)
–
The sensor
type must be
parameter-
ized
8
KTY-
–
X542:
1
DO 0.NC
Relay output for
changeover contact
Max. switching
voltage:
250 V AC, 30 V DC
Max. switching
power at 250 V AC:
2000 VA
Max. switching
power at 30 V DC:
240 W
–
NC contact
2
DO 0.COM
–
Basic
3
DO 0.NO
–
NO contact
4
DO 1.NC
Relay output for
changeover contact
Max. switching
voltage:
250 V AC, 30 V DC
Max. switching
power at 250 V AC:
2000 VA
Max. switching
power at 30 V DC:
240 W
–
NC contact
5
DO 1.COM
–
Basic
6
DO 1.NO
–
NO contact
Number of
Capacitor
Modules
Option
Additional cabinet width
per converter unit
DC link capacitance
per sub DC link
0
–
–
12 mF
1
N06
970 mm
18 mF
2
N07
1940 mm
24 mF
3
N08
2910 mm
30 mF
© Siemens AG 2012