Description of options
SINAMICS GM150, SINAMICS SM150
Description of options
6/34
Siemens D 12 · 2012
6
■
Options
M34
Connection of auxiliary voltage and signal cables from the top
(SINAMICS GM150 in the IGBT version)
Given suitable installation conditions, option
M34
enables the
auxiliary infeed and the signal cable to be introduced into the
cabinet unit from the top.
Note:
Option
M34
requires that option
M32
(customer's terminal strip
with spring-loaded terminals for signal cables up to 2.5 mm
2
) or
M33
(customer's terminal strip with screw terminals for signal
cables up to 2.5 mm
2
) must be simultaneously ordered.
M36
Brass cable entry for power cables
(SINAMICS GM150, SINAMICS SM150 in IGCT version)
With option
M36
the converter is supplied with a brass cable
entry for the power cables.
For versions with single-core cables, option
M36
is required,
so that no circulating currents form in the cable gland.
M42
IP42 degree of protection
(SINAMICS GM150 in the air-cooled IGBT version)
With option
M42
, the degree of protection of the air-cooled
converters can be enhanced (IP22 is standard). Additional
close-meshed grilles where the air comes in and goes out
prevent the ingress of solid matter with diameters > 1.0 mm.
M54
IP54 degree of protection
(SINAMICS GM150 in the water-cooled version and
SINAMICS SM150 in the IGCT version)
With option
M54
, the degree of protection of the water-cooled
converters can be enhanced (IP43 is standard).
M61
Redundant fan in the power unit
(SINAMICS GM150 in the IGBT version)
To improve system availability, it is possible to equip the con-
verter with an additional redundantly operating fan. If a fan within
the converter cabinet unit fails, this is immediately detected by
the differential pressure detector in the cabinet and the redun-
dant fan is activated by the converter controller without the con-
verter and hence the drive system failing. This enables produc-
tion down times or interruptions to be avoided and replacement
of the faulty fan to be postponed until the next scheduled shut-
down.
Note:
Option
M61
cannot be combined with option
L72
(Braking Module).
Note:
Option
M61
is not available for all converters.
For the following converters, the cabinet width must be
increased by 600 mm:
For the following converters, the cabinet width must be
increased by 600 mm and the air intake temperature must be
limited to a maximum of +35 °C:
The following converters cannot be ordered with option M61:
Rated voltage
Converter
2.3 kV
6SL3810-2LM36-0AA0
6SL3810-2LM37-0AA1
6SL3810-2LM38-0AA1
3.3 kV
6SL3810-2LN36-0AA0
6SL3810-2LN37-0AA1
6SL3810-2LN38-0AA1
4.16 kV
6SL3810-2LP35-3AA1
Rated voltage
Converter
4.16 kV
6SL3810-2LP36-0AA0
6SL3810-2LP37-0AA1
6SL3810-2LP38-0AA1
Rated voltage
Converter
3.3 kV
6SL3810-2LN41-4AA1
4.16 kV
6SL3810-2LP41-1AA0
6SL3810-2LP41-2AA1
6SL3810-2LP41-4AA1