SINAMICS GM150, SINAMICS SM150
Description of options
6/27
Siemens D 12 · 2012
6
■
Options
L72
Braking Module
In order to permit braking operation for Basic Infeed
(SINAMICS GM150) or for Active Infeed (SINAMICS SM150) to
be able to brake even if the power fails, a Braking Module with
braking resistor can be used. The mechanical design of the
Braking Module corresponds to that of a Motor Module; its actual
version is adapted to the converter cooling type (air or water
cooling).
The following should be ensured when engineering:
•
Shielded cables should be used just the same as at the
converter output.
•
The same maximum cable lengths as for SINAMICS GM150
in the IGBT version apply (without sine-wave filter or output
reactor;
refer to Power cables, Page 9/13
).
•
Regarding inductance
L
, the following requirements apply to
the braking resistor and cable routing: The time constant
L/R
must not exceed 20 μs, i.e.
L
must be less than
R
× 20
µ
s.
Note:
An external load resistor is connected as the braking resistor.
This is not included in the scope of supply
(option
Y73
see
Page 6/42)
.
Note:
Option
L72
cannot be combined with option
M61
(redundant fan
in the power unit).
Note:
For SINAMICS SM150 in IGCT version, option
L72
on request.
Note:
For SINAMICS GM150 in IGCT version, option
L72
cannot be
combined with option
N15
(24-pulse Basic Line Module).
Notice:
With option
L72
the cabinet width is increased as follows:
•
SINAMICS GM150 in the 12-pulse IGBT version: 600 mm
•
SINAMICS SM150 in the IGCT version: 1800 mm
Braking power of the Braking Module with external
braking resistor
Note:
The data in the table above apply for the maximum control of
the Braking Module. Different values for braking resistors are
available on request.
Power connections, braking resistor
Connections, temperature monitoring for braking resistor
Converter
output
voltage
Cooling
method
Required
braking
resistor
(± 10 %)
Braking
resistor
supply
voltage
Braking power
Braking Module
P
20
P
DB
kV
Ω
kV
kW
kW
SINAMICS GM150 in IGBT version
2.3
Air
9.5
4.1
1000
333
Water
7.5
4.1
1250
417
3.3
Air
13.5
5.8
1400
467
Water
11
5.8
1700
567
4.16
Air
17.5
7.5
1800
600
Water
14
7.5
2250
750
SINAMICS GM150 in IGCT version and
SINAMICS SM150 in IGCT version
3.3
Water
2 × 2.2
5.8
4000
1)
4000
Terminal
Significance
SINAMICS GM150 and SINAMICS SM150 in IGBT version
1C1
Power cable connection (+)
1D1
Power cable connection (–)
SINAMICS GM150 and SINAMICS SM150 in IGCT version
1C1
Power cable connection (+)
1D1
Power cable connection (–)
1M1
Power cable connection (0)
Terminal
Significance
SINAMICS GM150 and SINAMICS SM150 in IGBT version
=.CG-X11:1
24 V DC power supply
=.CG-X11:2
Braking resistor temperature too high, fault
=.CG-X11:3
Braking resistor temperature too high, alarm
=.CG-X11:5
Air flow switch ON (option
Y73
)
=.EF-X22:8
Reference ground
SINAMICS GM150 and SINAMICS SM150 in IGCT version
=.CG-X11:1
24 V DC power supply
=.CG-X11:2
Braking resistor temperature too high, fault
=.CG-X11:3
Braking resistor temperature too high, alarm
=.EF-X22:4
Reference ground
1)
Values can be higher for brief periods (in the range of seconds).