Description of options
6/12
Siemens D 12 · 2012
6
■
Options
E00
Closed-loop control for separately-excited synchronous
motors (static excitation unit is provided on the plant side)
When option
E00
is selected, the converter is supplied without
static excitation unit. The static excitation unit should be pro-
vided on the plant side.
E01
Closed-loop control for separately excited synchronous
motors with slipring excitation
(for static excitation units, see Accessories, Chapter 7)
If the converter is to be used to control separately excited syn-
chronous motors with slipring excitation, put the code
E01
in the
order. For slipring excitation, the exciter cabinet must also be
ordered. It has its own order number.
Note:
Converter and exciter cabinet must be ordered together.
Note:
For SINAMICS GM150, option
E01
on request.
E02
Closed-loop control for separately excited synchronous
motors with brushless excitation
(on request, for static excitation units, see Accessories,
Chapter 7)
If the converter is to be used to control separately excited
synchronous motors with brushless excitation, order code
E02
must be specified when ordering. For brushless excitation, the
exciter cabinet must also be ordered. It has its own order
number.
E03
Control for permanently-excited synchronous motors
If the converter is to be used to control permanently-excited syn-
chronous motors, order code
E03
must be included in the order.
Note:
Option
E03
requires that option
L52
is simultaneously ordered
(circuit breaker at converter output).
Note:
For SINAMICS SM150 in IGBT version and SINAMICS GM150,
option
E03
on request.
E11 to E71
(SINAMICS GM150, water-cooled)
Individual certification of the converter by the relevant
certifying organizations, including the extensions described
under option M66
Note:
It is not possible to combine several individual certificates.
Note:
For SINAMICS GM150 in IGBT version, the combination with
option
Y15
(sine-wave filter) on request.
E82
Increased frequency
(converter for high-speed rotors, SINAMICS GM150
in IGBT version)
When operated above 66 Hz, the converter should be classified
as a converter for high-speed rotors.
E86
Additional analog inputs (isolated)
With option
E86
an additional TM31 Terminal Module is avail-
able. Its analog inputs are isolated. Multirange transformers are
used (setting range: 0 V to 10 V; 0 mA to 20 mA or 4 mA to
20 mA).
Note:
Option
E86
cannot be combined with options
G62
(second
additional TM31 Terminal Module), as well as
L94
and
L96
(2 Pt100 evaluation units).
Option
Description
E11
Suitable for marine use with individual certificate from
Germanische Lloyd (GL)
includes option
M66
E21
Suitable for marine use with individual certificate from
Lloyds Register (LR)
includes option
M66
E31
Suitable for marine use with individual certificate from
Bureau Veritas (BV)
includes option
M66
E51
Suitable for marine use with individual certificate from
Det Norske Veritas (DNV)
includes option
M66
E61
Suitable for marine use with individual certificate from
the American Bureau of Shipping (ABS)
includes option
M66
E71
Suitable for marine use with individual certificate from
the Chinese Classification Society (CCS)
includes option
M66