SIEMENS
Description of options
SINAMICS GM150, SINAMICS SM150
Description of options
6/10
Siemens D 12 · 2012
6
■
Options
B43 to B45
Production flowcharts:
Production flowcharts are provided with options
B43 to B45
.
After the order has been clarified, these are sent as dual
language (English/German) PDF file by E-Mail.
C30 to C49
Auxiliary voltage other than N/400 V/3 AC
(SINAMICS GM150, SINAMICS SM150 in IGBT version)
A N/400 V/3 AC auxiliary supply must be provided on the plant
side to supply power for the fans, open-loop/closed-loop control,
protection and monitoring systems as well as the DC link pre-
charging. If the auxiliary supply in the plant differs from this
value, you must select one of the options
C30 to C49
. In this
case the three-phase infeed supply which differs from the stan-
dard version is adapted with three individual transformers to the
required voltage level. Tappings from 200 V 3 AC to 690 V 3 AC
are available for this purpose. The current required for the
auxiliary infeed supply can be determined from the data for
the current requirement at 400 V 3 AC (
see Technical
Specifications, Conversion to Existing Auxiliary Voltage
).
Note:
A matching transformer is necessary if 50 Hz 400 V 3 AC is
available on the plant side, however, without a neutral conductor
connection. In this case, option
C38
should be selected.
Exception: A separate 230 V supply can be provided for the
closed-loop control on the plant side.
Note:
For isolated systems the maximum supply voltage is 500 V 3 AC.
Note:
Access to the matching transformers is possible only from the
rear of the converter.
Option
Description
B43
Documentation, production flowchart: Generated once
B44
Documentation, production flowchart: Updated every
two weeks
B45
Documentation, production flowchart: Updated every month
Order codes for auxiliary voltages and line frequencies
C30
50 Hz 200 V 3 AC
C33
60 Hz 220 V 3 AC
C34
60 Hz 230 V 3 AC
C35
60 Hz 240 V 3 AC
C36
50 Hz 380 V 3 AC
C37
60 Hz 380 V 3 AC
C38
50 Hz 400 V 3 AC
C39
50 Hz 415 V 3 AC
C40
60 Hz 440 V 3 AC
C41
60 Hz 460 V 3 AC
C42
60 Hz 480 V 3 AC
C43
50 Hz 500 V 3 AC
C44
50 Hz 550 V 3 AC
C46
60 Hz 575 V 3 AC
C48
50 Hz 690 V 3 AC
C49
60 Hz 690 V 3 AC
Auxiliary voltage
infeed
Supply voltage for
= EA–Q11:1
L1
Fan, DC link precharging
= EA–Q11:3
L2
= EA–Q11:5
L3
= EB–X1:1
L1
Open-loop and closed-loop control,
protection and monitoring equipment
= EB–X1:2
N
© Siemens AG 2012