SIEMENS
5
SINAMICS GM150 in IGCT Tandem version
01/28/2015
© Siemens AG 2015
14
SINAMICS GM150 SINAMICS SM150
Supplement for Catalog D 12 2012
5.4
Technical data
Table 5-2
SINAMICS GM150 in IGCT tandem version, water cooling
Rated data
Order number: 6SL3835-…
...-2LR41-8AT0
1)
...-2LR42-1AT0
Output voltage
kV
2 x 3.3
2 x 3.3
Type rating
kVA
20000
24000
Rated output current
A
2 x 1750
2 x 2100
Shaft output
kW
16700
2)
19300
3)
20000
2)
23100
3)
hp
22700
2)
26200
3)
27000
2)
31400
3)
Input voltage
kV
2 x (2 x 1,7)
2 x (2 x 1,7)
Rated input current
A
2 x (2 x 1570)
2 x (2 x 1970)
Power loss
kW
approx. 2 x 110
approx. 2 x 110
Efficiency
%
99.1
99.1
Typ. current demand of the
auxiliary supply
230 V 1 AC 50/60 Hz
A
6
6
Max. current demand of the
auxiliary supply
400 V 3 AC 50/60 Hz
A
20
20
Precharging current
demand, briefly for approx. 25 s
A
40
40
Raw water flow rate
l/min
417
417
Deionized water requirement,
approx.
l
170
170
Sound pressure level L
pA
(1 m)
dB(A)
77
77
Measuring surface level L
S
(1 m) dB(A)
22
22
Cable cross-sections, line-side,
max. connectable per phase
mm
2
(DIN VDE)
6 x 240
6 x 240
AWG/MCM
(NEC,CEC)
6 x 500 MCM
6 x 500 MCM
Cable cross-sections, motor-
side, max. connectable per
phase
mm
2
(DIN VDE)
6 x 240
6 x 240
AWG/MCM
(NEC,CEC)
6 x 500 MCM
6 x 500 MCM
PE connection, max. con-
nection cross-section at the
enclosure with M12 screw
mm
2
(DIN VDE)
2 x 3 x 120
2 x 3 x 120
AWG/MCM
(NEC,CEC)
2 x 3 x 250 MCM
2 x 3 x 250 MCM
Degree of protection
–
IP43
IP43
Dimensions
Width
Height
Depth
mm
mm
mm
9400
2830
1600
9400
2830
1600
Weight
kg
9900
9900
1) On request
2) Power for operation of induction motors with typical power factor (cos
φ
)
motor
= 0.88 and efficiency
η
motor
= 0.96
3) Power for operation of synchronous motors with typical power factor (cos
φ
)
motor
= 1.0 and efficiency
η
motor
= 0.96