Technical specifications
Derating for special installation conditions
Current derating
If the converters are operated at installation altitudes above
1000 m above sea level or with intake temperatures in the
cooling unit > 35 °, derating factors
k
H
or
k
T
must be taken into
account for the rated current (DIN 43671). For the permitted
continuous current
I
:
I
≤
I
N
×
k
H
×
k
T
I
permitted continuous current
I
N
rated current
Current derating as a function of the installation altitude
(water cooling)
Derating factor
k
H
for water cooling
Current derating as a function of the raw water intake
temperature
Derating factor
k
T
(raw water intake temperature)
Voltage derating
For installation altitudes > 2000 m, acc. to
EN 60664-1/VDE 0110 (IEC 60664-1) in addition to a current
derating, a voltage derating is also required. This depends on
the air and creepage distances in the unit.
Voltage derating as a function of installation altitude
Derating factor
k
U
Example
Derating data SINAMICS GM150 in IGCT version
For the current, the following applies:
I
×
I
N
× 0.925 × 0.925 =
I
N
× 0.856
For the standard version, a current derating of 14.4 % is
required.
The maximum available output current is 1344 A for each
subsystem.
1000
2000
3000
4000
0
m
Correction factor
G_D012_EN_00028
k
H
0.9
0.8
0.6
1.0
0.7
Installation altitude above sea level
5
10
20
30
40
45
35
Correction factor
0.85
0.90
0.95
1.00
Raw-water inlet temperature
k
T
°C
G_D012_EN_00026a
Drive unit
6SL3835-2LN43-6AA0
Output voltage
3.3 kV
Input voltage
2 × (2 × 1.7) kV
Type rating
18000 kVA, 2 × 1570 A
Installation altitude
2000 m
Raw water intake temperature
40 °C
k
H
(water cooling)
0.925
k
T
(raw water intake temperature)
0.925
k
U
1.0
k
U
1000
2000
3000
4000
0
m
Correction factor
G_D012_EN_00029
0.9
0.8
0.6
1.0
0.7
Installation altitude above sea level