SIEMENS
SINAMICS GM150
Medium-Voltage Converter
SINAMICS GM150 in IGCT version
3/14
Siemens D 12 · 2012
3
■
Technical specifications
General technical data
Power components
Diodes, IGCTs
Line-side converter
• Standard
12-pulse diode rectifier (Basic Line Module)
• Option
24-pulse diode rectifier (Basic Line Module)
Motor-side converter
Inverter (Motor Module)
Closed-loop control
Closed-loop vector control
Drive quadrants
2 (2 directions of rotation, driving)
Electrical isolation, power unit/
open-loop and closed-loop control
Closed-loop vector control, insulating transformer
Auxiliary power supply
(for fans, coolant pumps,
precharging the DC link capacitors,
open-loop and closed-loop control)
230 V 1 AC ±10 %, 50/60 Hz ±3 % and
400 V 3 AC ±10 %, 50/60 Hz ±3 %
or another auxiliary voltage (options
C30 to C55
)
Installation altitude
≤
1000 m above sea level: 100 % load capability
>1000 ... 4000 m above sea level: current derating required
>2000 ... 4000 m above sea level: voltage derating required in addition
Insulation
According to EN 50178/VDE 0160 (IEC 62103): Pollution degree 2 (without conductive pollution),
condensation not permissible
Degree of protection
According to EN 60529/VDE 0470 T1 (IEC 60529): IP43
Protection class
I acc. to EN 61800-5-1/VDE 0160 T105 (IEC 61800-5-1)
Shock-hazard protection
EN 50274/VDE 0660 T514 and BGV A3 when used for the intended application
Interference transmission
This drive unit is part of a PDS, Category C4 acc. to EN 61800-3/VDE 0160 T103 (IEC 61800-3). It has not
been designed to be connected to the public line supply. EMC disturbances can occur when connected to
these line supplies. The essential requirements placed on EMC protection for the drive system should be
secured using an EMC plan on the customer side.
Paint finish/color
Indoor requirements/RAL 7035, light gray
Applicable standards and
directives
• Standards
EN 61800-3/VDE 0160 T103 (IEC 61800-3)
EN 61800-4/VDE 0160 T104 (IEC 61800-4), however, only if referenced in the standards EN 61800-3
or EN 61800-5-1
EN 61800-5-1/VDE 0160 T105 (IEC 61800-5-1)
EN 60146-1-1/VDE 0558 T11 (IEC 60146-1-1)
EN 50178/VDE 0160 (IEC 62103)
EN 60204-11/VDE 0113 T11 (IEC 60204-11), however, structuring principles and reference marking accord-
ing to EN 61346-1 instead of EN 81346-1
• EU directives
2006/95/EC + amendments (Low Voltage Directive)
2004/108/EC + amendments (Electromagnetic Compatibility)
Water cooling
Water-water cooling unit, internal circuit, deionized water
Permissible coolant temperature
(raw water)
• Inlet
5 ... 35 °C
• Discharge, max.
40 °C
Rated data
Output voltage
3.3 kV
Input voltage
2 × 1.7 kV
Tolerance of input voltage
±10 %
Line frequency
50/60 Hz ± 3 %
Line power factor fundamental
mode
> 0.96
© Siemens AG 2012