SIEMENS
SINAMICS GM150
Medium-Voltage Converter
SINAMICS GM150 in IGBT version
Water cooling, with sine-wave filter
2/45
Siemens D 12 · 2012
2
■
Technical specifications
SINAMICS GM150 in IGBT version
Water cooling, with sine-wave filter
(option Y15)
6SL3815-
2LN33-5AA0
6SL3815-
2LN34-0AA0
6SL3815-
2LN34-5AA0
6SL3815-
2LN35-0AA0
6SL3815-
2LN35-5AA0
Output voltage 3.3 kV
Type rating
kVA
1550
1750
2000
2150
2350
Shaft output
1)
kW
1300
1450
1650
1800
1950
hp
1750
2000
2250
2500
2750
Rated output current
A
270
310
350
380
410
Input voltage
kV
2 × 1.7
2 × 1.7
2 × 1.7
2 × 1.7
2 × 1.7
Rated input current
1)
A
2 × 234
2 × 269
2 × 307
2 × 346
2 × 370
Power loss
2) 3)
kW
29
32
36
40
42
Efficiency
3)
%
97.8
97.9
98.0
98.0
98.1
Typ. current demand
of the auxiliary supply
230 V 1 AC, 50/60 Hz
4)
A
2.5
2.5
2.5
2.5
2.5
Max. current demand
of the auxiliary supply
400 V 3 AC, 50/60 Hz
5)
A
31
31
31
31
31
Raw water flow rate
l/min
183
183
183
183
183
Deionized water require-
ment, approx.
l
100
100
100
100
100
Sound pressure level
L
pA
(1 m)
dB
74
74
74
74
74
Measuring surface level
L
s
(1 m)
dB
18
18
18
18
18
Cable cross-sections,
line-side, max.
connectable per phase
6) 7)
mm
2
(DIN VDE)
4 × 240
4 × 240
4 × 240
4 × 240
4 × 240
AWG/MCM
(NEC, CEC)
4 × 500 MCM
4 × 500 MCM
4 × 500 MCM
4 × 500 MCM
4 × 500 MCM
Cable cross-sections,
motor-side, max.
connectable per phase
6) 7)
mm
2
(DIN VDE)
3 × 240
3 × 240
3 × 240
3 × 240
3 × 240
AWG/MCM
(NEC, CEC)
3 × 500 MCM
3 × 500 MCM
3 × 500 MCM
3 × 500 MCM
3 × 500 MCM
PE connection,
max. connection cross-
section at the enclosure
with M12 screw
6)
mm
2
(DIN VDE)
4 × 240
4 × 240
4 × 240
4 × 240
4 × 240
AWG/MCM
(NEC, CEC)
4 × 500 MCM
4 × 500 MCM
4 × 500 MCM
4 × 500 MCM
4 × 500 MCM
Degree of protection
IP43
IP43
IP43
IP43
IP43
Dimensions
8)
• Width
mm
4540
4840
4840
4840
4840
• Height
mm
2280
2280
2280
2280
2280
• Depth
mm
1275
1275
1275
1275
1275
Circuit version
(Page 2/5)
Fig. No.
(
(
(
(
(
Weight
8)
kg
4000
4200
4200
4200
4300
1)
The data for the rated input current and the power data in hp and kW are
approximate values only; these have been calculated for operation with
induction motors and for a typical motor power factor cos
ϕ
and motor
efficiency. The calculation is based on the rated output current. In this
case, the kW and hp values lie in a power range, which is obtained by
selecting the following values: Motor power factor between 0.85 and 0.88
and a motor efficiency of 96 %. The rated input current also depends on
the line power factor, for which a typical value of between 0.94 and 0.96
was assumed.
The hp data are based on the NEC and CEC guidelines for the North
American market. The kW values are specified in multiples of 50. Both
approximate values need to be adapted to the motor which is actually
used.
2)
Approx. 5 % of the power loss is dissipated in the room.
3)
Without cooling system
4)
The typical current drawn (rms value; cos
ϕ
typ.
= 0.6) of the supply for the
converter open-loop/closed-loop control is specified. The separate sup-
plies for the socket outlets/light or switched auxiliary power feeders
(options
N35 to N38
) have not been taken into account. Values for the
typical current drawn for special configurations (e.g. for dimensioning an
upstream UPS) are available on request.
When using options
L48
(make-proof grounding switch at the converter
input),
L49
(make-proof grounding switch at the converter output) or
L51
(disconnector at the converter output), it should further be taken into
account that for switching operations, additional peak values of up to 10 A
can occur for each make-proof grounding switch or disconnector. This cor-
responds to the starting current of a motor used to operate a switch, which
decays from approx. 10 A to approx. 2 A in 200 ms. A switching operation
takes a total time of approx. 2 s. All optionally used make-proof grounding
switches or disconnectors are controlled via the manually-actuated make-
proof grounding switch for the converter DC link (standard) and therefore
switch simultaneously!
5)
Additional 20 A precharging current for 25 s.
6)
Data refer to a sub-system; for details about the number of sub-systems to
be connected on the line or motor side,
see Circuit versions, Page 2/5
.
7)
The maximum permissible cable lengths must be observed (
see Power
cables, Page 9/13
).
8)
The specified dimensions and weights include doors, panels, cooling unit
and sine-wave filter (option
Y15
), however no additional options.
© Siemens AG 2012