SIEMENS
SINAMICS G180
SINAMICS G180 cabinet units
SINAMICS G180 cabinet units
air-cooled and liquid-cooled
3/34
Siemens D 18.1 · 2014
3
■
Technical data
(continued)
690 V, 12-pulse
(continued)
Line voltage, supply system type
2 × 400, 415, 460, 500, 575,
690
V 3 AC IT
SINAMICS G180
cabinet units – air-cooled
6SE0180-
2DH42-2
■
A7
6SE0180-
2DH42-4
■
A7
6SE0180-
2DH42-7
■
A7
6SE0180-
2DH43-0
■
A7
6SE0180-
2EH43-2
■
A7
Converter type
(air-cooled)
2T3F-87603-920
2T3F-87603-923
2T3F-87603-926
2T3F-87603-929
2T3F-87604-931
SINAMICS G180
cabinet units – liquid-cooled
6SE0170-
2DH42-2
■
A7
6SE0170-
2DH42-4
■
A7
6SE0170-
2DH42-7
■
A7
6SE0170-
2DH43-0
■
A7
6SE0170-
2EH43-2
■
A7
Converter type
(liquid-cooled)
2T6F-77603-920
2T6F-77603-923
2T6F-77603-926
2T6F-77603-929
2T6F-77604-931
Electrical data at motor end
Type rating
1)
• at 50 Hz 690 V
kW
2000
2300
2600
2900
3100
• at 60 Hz 575 V
hp
2235
2570
2906
3241
3465
Output voltage
2)
V
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
Output current
• Continuous current
A
2140
2400
2710
2970
3200
• Short-time current
(60 s every 10 minutes) max.
A
2540
2800
3030
3230
3730
Overload capability
(60 s every 10 minutes) max.
%
19
17
12
9
17
Output power
kVA
2558
2868
3239
3549
3824
Output frequency, max.
Hz
120
120
120
120
120
Rated clock cycle
kHz
2.4
2.4
2.4
2.4
2.4
adjustable from
kHz
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss
3)
kW
50.9
57.2
64.5
73.9
77.3
Rated efficiency
%
97.7
97.7
97.7
97.6
97.7
Electrical data at line end
Connected load
kVA
2369
2648
2983
3272
3516
Rated input voltage
V
2 × 690
2 × 690
2 × 690
2 × 690
2 × 690
Input current
• Continuous line current
A
2 × 991
2 × 1108
2 × 1248
2 × 1369
2 × 1471
• Short-time line current (60 s) max.
A
2 × 1176
2 × 1293
2 × 1395
2 × 1489
2 × 1715
Line fuse (provided by customer)
gL (A)
1250
1250
1500
1600
1800
λ
line
0.997
0.997
0.997
0.997
0.997
Cos
ϕ
line
1
1
1
1
1
Radio interference suppression
acc. to EN 61800-3
C4
C4
C4
C4
C4
Mechanical data for air-cooled cabinet units
Frame size
(dimensional drawing classification)
SL7
SL7
SL7
SL7
SL8
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
78
78
78
78
79
Standard converter dimensions
• Width
mm
4806
4806
4806
4806
6406
• Height
4)
mm
2112
2112
2112
2112
2112
• Depth
mm
605
605
605
605
605
Coolant requirements
m
3
/h
11400
9600
11400
11400
12800
Weight, approx.
kg
2700
2790
2940
3090
3720
Mechanical data for liquid-cooled cabinet units
Frame size
(dimensional drawing classification)
SW7
SW7
SW7
SW7
SW8
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
76
76
76
76
77
Standard converter dimensions
• Width
mm
5206
5206
5206
5206
7006
• Height
mm
2202
2202
2202
2202
2202
• Depth
mm
605
605
605
605
605
Coolant requirements
l/h
6000
6000
6000
6000
8000
Min. coolant pressure
bar
2.5
2.5
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
6
6
Coolant test pressure
bar
10
10
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
10
10
Max. coolant temperature
°C
35
35
30
28
35
Weight, approx.
kg
2750
2850
2850
3100
3850
For footnotes, see next page.