SIEMENS
SINAMICS G180
SINAMICS G180 cabinet units
SINAMICS G180 cabinet units
air-cooled and liquid-cooled
3/32
Siemens D 18.1 · 2014
3
■
Technical data
(continued)
690 V, 12-pulse
(continued)
Line voltage, supply system type
2 × 400, 415, 460, 500, 575,
690
V 3 AC IT
SINAMICS G180
cabinet units – air-cooled
6SE0180-
2CH41-2
■
A7
6SE0180-
2CH41-3
■
A7
6SE0180-
2CH41-5
■
A7
6SE0180-
2CH41-7
■
A7
6SE0180-
2CH42-0
■
A7
Converter type
(air-cooled)
2T3F-87602-912
2T3F-87602-913
2T3F-87602-915
2T3F-87602-917
2T3F-87602-919
SINAMICS G180
cabinet units – liquid-cooled
6SE0170-
2CH41-2
■
A7
6SE0170-
2CH41-3
■
A7
6SE0170-
2CH41-5
■
A7
6SE0170-
2CH41-7
■
A7
6SE0170-
2CH42-0
■
A7
Converter type
(liquid-cooled)
2T6F-77602-912
2T6F-77602-913
2T6F-77602-915
2T6F-77602-917
2T6F-77602-919
Electrical data at motor end
Type rating
1)
• at 50 Hz 690 V
kW
1200
1300
1500
1700
1900
• at 60 Hz 575 V
hp
1341
1453
1676
1900
2123
Output voltage
2)
V
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
Output current
• Continuous current
A
1260
1430
1600
1810
1980
• Short-time current
(60 s every 10 minutes) max.
A
1520
1700
1870
2020
2150
Overload capability
(60 s every 10 minutes) max.
%
21
19
17
12
9
Output power
kVA
1506
1709
1912
2163
2366
Output frequency, max.
Hz
120
120
120
120
120
Rated clock cycle
kHz
2.4
2.4
2.4
2.4
2.4
adjustable from
kHz
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss
3)
kW
28.2
33.6
37.5
42.6
46.5
Rated efficiency
%
97.8
97.7
97.7
97.7
97.7
Electrical data at line end
Connected load
kVA
1405
1597
1781
2010
2194
Rated input voltage
V
2 × 690
2 × 690
2 × 690
2 × 690
2 × 690
Input current
• Continuous line current
A
2 × 588
2 × 668
2 × 745
2 × 841
2 × 918
• Short-time line current (60 s) max.
A
2 × 709
2 × 794
2 × 871
2 × 939
2 × 997
Line fuse (provided by customer)
gL (A)
800
800
900
1000
1250
λ
line
0.997
0.997
0.997
0.997
0.997
Cos
ϕ
line
1
1
1
1
1
Radio interference suppression
acc. to EN 61800-3
C4
C4
C4
C4
C4
Mechanical data for air-cooled cabinet units
Frame size
(dimensional drawing classification)
SL4
SL4
SL4
SL4
SL4
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
77
77
77
77
77
Standard converter dimensions
• Width
mm
3206
3206
3206
3206
3206
• Height
4)
mm
2112
2112
2112
2112
2112
• Depth
mm
605
605
605
605
605
Coolant requirements
m
3
/h
6400
7600
6400
7600
7600
Weight, approx.
kg
1780
1800
1860
1960
2060
Mechanical data for liquid-cooled cabinet units
Frame size
(dimensional drawing classification)
SW4
SW4
SW4
SW4
SW4
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
75
75
75
75
75
Standard converter dimensions
• Width
mm
3606
3606
3606
3606
3606
• Height
mm
2202
2202
2202
2202
2202
• Depth
mm
605
605
605
605
605
Coolant requirements
l/h
4000
4000
4000
4000
4000
Min. coolant pressure
bar
2.5
2.5
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
6
6
Coolant test pressure
bar
10
10
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
10
10
Max. coolant temperature
°C
35
35
35
30
28
Weight, approx.
kg
1840
1860
1920
2020
2120
For footnotes, see next page.
© Siemens AG 2014