SIEMENS
SINAMICS G180
SINAMICS G180 cabinet units
SINAMICS G180 cabinet units
air-cooled and liquid-cooled
3/28
Siemens D 18.1 · 2014
3
■
Technical data
(continued)
690 V, 12-pulse
Line voltage, supply system type
2 × 400, 415, 460, 500, 575,
690
V 3 AC IT
SINAMICS G180
cabinet units – air-cooled
6SE0180-
2BH33-2
■
A7
6SE0180-
2BH33-6
■
A7
6SE0180-
2BH34-2
■
A7
6SE0180-
2BH35-2
■
A7
6SE0180-
2BH35-7
■
A7
Converter type
(air-cooled)
2T3F-87601-250
2T3F-87601-315
2T3F-87601-400
2T3F-87601-500
2T3F-87601-560
SINAMICS G180
cabinet units – liquid-cooled
6SE0170-
2BH33-2
■
A7
6SE0170-
2BH33-6
■
A7
6SE0170-
2BH34-2
■
A7
6SE0170-
2BH35-2
■
A7
6SE0170-
2BH35-7
■
A7
Converter type
(liquid-cooled)
2T6F-77601-250
2T6F-77601-315
2T6F-77601-400
2T6F-77601-500
2T6F-77601-560
Electrical data at motor end
Type rating
1)
• at 50 Hz 690 V
kW
250
315
400
500
560
• at 60 Hz 575 V
hp
279
352
447
559
626
Output voltage
2)
V
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
Output current
• Continuous current
A
270
340
440
530
590
• Short-time current
(60 s every 10 minutes) max.
A
320
410
510
640
710
Overload capability
(60 s every 10 minutes) max.
%
19
21
16
21
20
Output power
kVA
323
406
526
633
705
Output frequency, max.
Hz
250
250
250
120
120
Rated clock cycle
kHz
3
3
2.4
2.4
2.4
adjustable from
kHz
2 ... 5
2 ... 5
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss
3)
kW
6.15
7.73
9.37
12.2
13.7
Rated efficiency
%
97.7
97.7
97.8
97.7
97.7
Electrical data at line end
Connected load
kVA
311
392
502
600
667
Rated input voltage
V
2 × 690
2 × 690
2 × 690
2 × 690
2 × 690
Input current
• Continuous line current
A
2 × 130
2 × 164
2 × 210
2 × 251
2 × 279
• Short-time line current (60 s) max.
A
2 × 154
2 × 198
2 × 243
2 × 303
2 × 336
Line fuse (provided by customer)
gL (A)
160
200
250
315
315
λ
line
0.995
0.995
0.995
0.997
0.997
Cos
ϕ
line
1
1
1
1
1
Radio interference suppression
acc. to EN 61800-3
C4
C4
C4
C4
C4
Mechanical data for air-cooled cabinet units
Frame size
(dimensional drawing classification)
SL5
SL5
SL5
SL5
SL6
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
70
70
70
75
75
Standard converter dimensions
• Width
mm
1406
1406
1406
1406
1806
• Height
4)
mm
2112
2112
2112
2112
2112
• Depth
mm
605
605
605
605
605
Coolant requirements
m
3
/h
1900
1900
1900
2650
3200
Weight, approx.
kg
690
710
730
810
920
Mechanical data for liquid-cooled cabinet units
Frame size
(dimensional drawing classification)
SW5
SW5
SW5
SW5
SW6
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
68
68
68
73
73
Standard converter dimensions
• Width
mm
1406
1406
1406
1406
2006
• Height
mm
2202
2202
2202
2202
2202
• Depth
mm
605
605
605
605
605
Coolant requirements
l/h
1200
1200
1200
1200
2000
Min. coolant pressure
bar
2.5
2.5
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
6
6
Coolant test pressure
bar
10
10
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
10
10
Max. coolant temperature
°C
35
35
35
30
35
Weight, approx.
kg
690
710
730
810
950
For footnotes, see next page.
© Siemens AG 2014