SIEMENS
SINAMICS G180
SINAMICS G180 cabinet units
SINAMICS G180 cabinet units
air-cooled and liquid-cooled
3/24
Siemens D 18.1 · 2014
3
■
Technical data
(continued)
690 V, 6-pulse
(continued)
Line voltage, supply system type
400, 415, 460, 500, 575,
690
V 3 AC TT/TN or IT
SINAMICS G180
cabinet units – air-cooled
6SE0180-
1B
■
36-4
■
A7
6SE0180-
1B
■
37-1
■
A7
6SE0180-
1B
■
37-7
■
A7
6SE0180-
1B
■
41-0
■
A7
6SE0180-
1B
■
41-1
■
A7
Converter type
(air-cooled)
2T3A-87601-630
2T3A-87601-710
2T3A-87601-800
2T3A-87601-909
2T3A-87601-910
SINAMICS G180
cabinet units – liquid-cooled
6SE0170-
1B
■
36-4
■
A7
6SE0170-
1B
■
37-1
■
A7
6SE0170-
1B
■
37-7
■
A7
6SE0170-
1B
■
41-0
■
A7
6SE0170-
1B
■
41-1
■
A7
Converter type
(liquid-cooled)
2T6A-77601-630
2T6A-77601-710
2T6A-77601-800
2T6A-77601-909
2T6A-77601-910
Electrical data at motor end
Type rating
1)
• at 50 Hz 690 V
kW
630
710
800
900
1000
• at 60 Hz 575 V
hp
704
794
894
1006
1118
Output voltage
2)
V
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
Output current
• Continuous current
A
660
750
840
950
1040
• Short-time current
(60 s every 10 minutes) max.
A
800
890
980
1060
1130
Overload capability
(60 s every 10 minutes) max.
%
21
19
17
12
9
Output power
kVA
789
896
1004
1135
1243
Output frequency, max.
Hz
120
120
120
120
120
Rated clock cycle
kHz
2.4
2.4
2.4
2.4
2.4
adjustable from
kHz
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss
3)
kW
15.4
16.6
18.7
21
23.3
Rated efficiency
%
97.7
97.8
97.8
97.8
97.8
Electrical data at line end
Connected load
kVA
764
854
956
1078
1165
Rated input voltage
V
690
690
690
690
690
Input current
• Continuous line current
A
639
715
800
902
975
• Short-time line current (60 s) max.
A
774
848
933
1006
1059
Line fuse (provided by customer)
gL (A)
800
800
900
1000
1000
λ
line
0.942
0.944
0.945
0.947
0.949
Cos
ϕ
line
1
1
1
1
1
Radio interference suppression
acc. to EN 61800-3
4)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
Mechanical data for air-cooled cabinet units
Frame size
(dimensional drawing classification)
SL3
SL3
SL3
SL3
SL3
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
75
75
75
75
75
Standard converter dimensions
• Width
mm
1606
1606
1606
1606
1606
• Height
5)
mm
2112
2112
2112
2112
2112
• Depth
mm
605
605
605
605
605
Coolant requirements
m
3
/h
3200
3800
3200
3800
3800
Weight, approx.
kg
890
900
930
980
1030
Mechanical data for liquid-cooled cabinet units
Frame size
(dimensional drawing classification)
SW3
SW3
SW3
SW3
SW3
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
73
73
73
73
73
Standard converter dimensions
• Width
mm
1806
1806
1806
1806
1806
• Height
mm
2202
2202
2202
2202
2202
• Depth
mm
605
605
605
605
605
Coolant requirements
l/h
2000
2000
2000
2000
2000
Min. coolant pressure
bar
2.5
2.5
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
6
6
Coolant test pressure
bar
10
10
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
10
10
Max. coolant temperature
°C
35
35
35
30
28
Weight, approx.
kg
920
930
960
1010
1060
For footnotes, see next page.