Technical data
(continued)
Line voltage, supply system type
400, 415, 460, 500, 575,
690
V 3 AC TT/TN or IT
SINAMICS G180
cabinet units – air-cooled
6SE0180-
1B
■
33-2
■
A7
6SE0180-
1B
■
33-6
■
A7
6SE0180-
1B
■
34-2
■
A7
6SE0180-
1B
■
35-2
■
A7
6SE0180-
1B
■
35-7
■
A7
Converter type
(air-cooled)
2T3A-87601-250
2T3A-87601-315
2T3A-87601-400
2T3A-87601-500
2T3A-87601-560
SINAMICS G180
cabinet units – liquid-cooled
6SE0170-
1B
■
33-2
■
A7
6SE0170-
1B
■
33-6
■
A7
6SE0170-
1B
■
34-2
■
A7
6SE0170-
1B
■
35-2
■
A7
6SE0170-
1B
■
35-7
■
A7
Converter type
(liquid-cooled)
2T6A-77601-250
2T6A-77601-315
2T6A-77601-400
2T6A-77601-500
2T6A-77601-560
General mechanical data
Max. cable length between converter
and motor with standard insulation
(shielded)
m
100/250
6)
100/250
6)
100/250
6)
100/250
6)
100/250
7)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections,
see "Cable cross-sections and
connections" in section
"Configuring instructions"
Approvals, according to
NRTL
8)
NRTL
8)
NRTL
8)
NRTL
8)
NRTL
8)
1)
Rated power of a typical 2- to 6-pole standard motor.
2)
Typical output voltage dependent on filter and unit type.
3)
Maximum power loss with continuous motor current.
4)
EMC filter not required for IT system, in which case RI suppression
category C4.
5)
With IP21 protective top cover (110 mm).
6)
Value is applicable with option L10 (strengthened d
v
/d
t
filter;
filter is integrated in additional 400 mm cabinet).
7)
Value is applicable with option L10 (strengthened d
v
/d
t
filter;
filter is integrated in unit).
8)
On request; the voltage range for NRTL units ends at max. 600 V.
© Siemens AG 2014