SIEMENS
SINAMICS G180
SINAMICS G180 cabinet units
SINAMICS G180 cabinet units
air-cooled and liquid-cooled
3/20
Siemens D 18.1 · 2014
3
■
Technical data
(continued)
500 V, 12-pulse
(continued)
Line voltage, supply system type
2 × 400, 415, 460,
500
V 3 AC IT
SINAMICS G180
cabinet units – air-cooled
6SE0180-
2BD38-8
■
A7
6SE0180-
2BD41-0
■
A7
6SE0180-
2BD41-1
■
A7
Converter type
(air-cooled)
2T3F-87501-630
2T3F-87501-710
2T3F-87501-800
SINAMICS G180
cabinet units – liquid-cooled
6SE0170-
2BD38-8
■
A7
6SE0170-
2BD41-0
■
A7
6SE0170-
2BD41-1
■
A7
Converter type
(liquid-cooled)
2T6F-77501-630
2T6F-77501-710
2T6F-77501-800
Electrical data at motor end
Type rating
1)
• at 50 Hz 500 V
kW
630
710
800
• at 60 Hz 460 V
hp
777
876
987
Output voltage
2)
V
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
Output current
• Continuous current
A
920
1030
1150
• Short-time current
(60 s every 10 minutes) max.
A
1100
1230
1380
Overload capability
(60 s every 10 minutes) max.
%
20
19
20
Output power
kVA
797
892
996
Output frequency, max.
Hz
120
120
120
Rated clock cycle
kHz
2.4
2.4
2.4
adjustable from
kHz
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss
3)
kW
15.4
18.1
20.3
Rated efficiency
%
97.7
97.6
97.6
Electrical data at line end
Connected load
kVA
767
849
944
Rated input voltage
V
2 × 500
2 × 500
2 × 500
Input current
• Continuous line current
A
2 × 443
2 × 490
2 × 545
• Short-time line current (60 s) max.
A
2 × 530
2 × 585
2 × 654
Line fuse (provided by customer)
gL (A)
500
630
630
λ
line
0.996
0.996
0.997
Cos
ϕ
line
1
1
1
Radio interference suppression
acc. to EN 61800-3
C4
C4
C4
Mechanical data for air-cooled cabinet units
Frame size
(dimensional drawing classification)
SL6
SL6
SL6
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
75
75
75
Standard converter dimensions
• Width
mm
1806
1806
1806
• Height
4)
mm
2112
2112
2112
• Depth
mm
605
605
605
Coolant requirements
m
3
/h
3800
3200
3800
Weight, approx.
kg
930
960
1010
Mechanical data for liquid-cooled cabinet units
Frame size
(dimensional drawing classification)
SW6
SW6
SW6
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
73
73
73
Standard converter dimensions
• Width
mm
2006
2006
2006
• Height
mm
2202
2202
2202
• Depth
mm
605
605
605
Coolant requirements
l/h
2000
2000
2000
Min. coolant pressure
bar
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
Coolant test pressure
bar
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
Max. coolant temperature
°C
35
35
30
Weight, approx.
kg
960
990
1040
For footnotes, see next page.
© Siemens AG 2014