SIEMENS
SINAMICS G180
SINAMICS G180 cabinet units
SINAMICS G180 cabinet units
air-cooled and liquid-cooled
3/10
Siemens D 18.1 · 2014
3
■
Technical data
(continued)
400 V, 12-pulse
Line voltage, supply system type
400
, 415 V 3 AC IT
SINAMICS G180
cabinet units – air-cooled
6SE0180-
2BA33-7
■
A7
6SE0180-
2BA34-6
■
A7
6SE0180-
2BA36-3
■
A7
6SE0180-
2BA37-3
■
A7
6SE0180-
2BA38-8
■
A7
Converter type
(air-cooled)
2T3F-87401-200
2T3F-87401-250
2T3F-87401-315
2T3F-87401-400
2T3F-87401-500
SINAMICS G180
cabinet units – liquid-cooled
6SE0170-
2BA33-7
■
A7
6SE0170-
2BA34-6
■
A7
6SE0170-
2BA36-3
■
A7
6SE0170-
2BA37-3
■
A7
6SE0170-
2BA38-8
■
A7
Converter type
(liquid-cooled)
2T6F-77401-200
2T6F-77401-250
2T6F-77401-315
2T6F-77401-400
2T6F-77401-500
Electrical data at motor end
Type rating
1)
• at 50 Hz 400 V
kW
200
250
315
400
500
• at 50 Hz 400 V
hp
268
335
422
536
671
Output voltage
2)
V
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
Output current
• Continuous current
A
380
460
630
740
910
• Short-time current
(60 s every 10 minutes) max.
A
470
560
700
900
1110
Overload capability
(60 s every 10 minutes) max.
%
24
22
11
22
22
Output power
kVA
263
319
436
513
630
Output frequency, max.
Hz
250
250
250
120
120
Rated clock cycle
kHz
3
3
3
2.4
2.4
adjustable from
kHz
2 ... 5
2 ... 5
2 ... 5
1.5 ... 3.7
1.5 ... 3.7
Power loss
3)
kW
5.6
6.42
8.4
11.9
14.9
Rated efficiency
%
97.4
97.6
97.5
97.2
97.2
Electrical data at line end
Connected load
kVA
249
301
405
477
604
Rated input voltage
V
400
400
400
400
400
Input current
• Continuous line current
A
180
217
292
344
436
• Short-time line current (60 s) max.
A
223
264
324
418
532
Line fuse (provided by customer)
gL (A)
200
250
400
400
500
λ
line
0.994
0.994
0.994
0.996
0.996
Cos
ϕ
line
1
1
1
1
1
Radio interference suppression
acc. to EN 61800-3
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
Mechanical data for air-cooled cabinet units
Frame size
(dimensional drawing classification)
SL5
SL5
SL5
SL5
SL6
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
70
70
73
75
75
Standard converter dimensions
• Width
mm
1406
1406
1406
1406
1806
• Height
4)
mm
2112
2112
2112
2112
2112
• Depth
mm
605
605
605
605
605
Coolant requirements
m
3
/h
1900
1900
1900
2250
3800
Weight, approx.
kg
690
710
730
810
920
Mechanical data for liquid-cooled cabinet units
Frame size
(dimensional drawing classification)
SW5
SW5
SW5
SW5
SW6
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
68
68
71
73
73
Standard converter dimensions
• Width
mm
1406
1406
1406
1406
2006
• Height
mm
2202
2202
2202
2202
2202
• Depth
mm
605
605
605
605
605
Coolant requirements
l/h
1200
1200
1200
1200
2000
Min. coolant pressure
bar
2.5
2.5
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
6
6
Coolant test pressure
bar
10
10
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
10
10
Max. coolant temperature
°C
35
35
35
30
35
Weight, approx.
kg
690
710
730
810
950
For footnotes, see next page.
© Siemens AG 2014