SIEMENS
SINAMICS G180
SINAMICS G180 compact units and SINAMICS G180 cabinet systems
SINAMICS G180 compact units
2/14
Siemens D 18.1 · 2014
2
■
Technical data
(continued)
690 V, 6-pulse
(continued)
Line voltage, supply system type
230 ... 690 V 3 AC, TT/TN or IT
SINAMICS G180
compact units
6SE0100-
1A
■
31-2
■
A7
6SE0100-
1A
■
31-4
■
A7
6SE0100-
1A
■
31-7
■
A7
6SE0100-
1A
■
32-1
■
A7
Converter type
2T2A-07600-110
2T2A-07600-132
2T2A-07600-160
2T2A-07600-200
Electrical data at motor end
Type rating
1)
• at 50 Hz 690 V
kW
110
132
160
200
• at 60 Hz 575 V
hp
122
148
179
224
Output voltage
2)
V
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
Output current
• Continuous current
A
120
150
175
210
• Short-time current
(60 s every 10 minutes) max.
A
140
175
210
255
Overload capability
(60 s every 10 minutes) max.
%
17
17
20
21
Output power
kVA
143
179
209
251
Output frequency, max.
Hz
250
250
250
250
Rated clock cycle
kHz
3
3
3
3
adjustable from
kHz
2 ... 5
2 ... 5
2 ... 5
2 ... 5
Power loss
3)
kW
3.21
3.7
4.48
5.38
Rated efficiency
%
97.3
97.4
97.4
97.5
Electrical data at line end
Connected load
kVA
57.5
74.8
98.4
119
Rated input voltage
V
690
690
690
690
Input current
• Continuous line current
A
119
153
180
222
• Short-time line current (60 s)
max.
A
139
178
216
270
Line fuse
(provided by customer)
gL (A)
125 ... 160
160 ... 200
200 ... 250
250 ... 315
λ
line
0.883
0.857
0.862
0.838
Cos
ϕ
line
1
1
1
1
Radio interference suppres-
sion acc. to EN 61800-3
C2 (class A filter)
C2 (class A filter)
C2 (class A filter)
C2 (class A filter)
Mechanical data
Coolant requirements
m
3
/h
1050
1050
1600
1600
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
62
62
64
64
Max. cable length between
converter and motor with
standard insulation
• (shielded)
m
150/300
4)
150/300
4)
150/300
4)
150/300
4)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections,
see "Cable cross-sections and
connections" in section
"Configuring instructions"
Dimensions
• Width
mm
350
350
500
500
• Height
(without mounting brackets)
mm
1060
1060
1060
1060
• Depth
mm
320
320
320
320
Weight, approx.
kg
94
96
170
180
Approvals, according to
NRTL
5)
NRTL
5)
NRTL
5)
NRTL
5)
Frame size
K5
K5
K6
K6
1)
Rated power of a typical 2- to 6-pole standard motor.
2)
Typical output voltage dependent on filter and unit type.
3)
Maximum power loss with continuous current.
4)
Value is applicable with option L10 (strengthened d
v
/d
t
filter;
strengthened filter is supplied separately with unit).
5)
On request; the voltage range for NRTL units ends at max. 600 V.
© Siemens AG 2014