SIEMENS
SINAMICS G180
SINAMICS G180 compact units and SINAMICS G180 cabinet systems
SINAMICS G180 compact units
2/12
Siemens D 18.1 · 2014
2
■
Technical data
(continued)
690 V, 6-pulse
Line voltage, supply system type
230 ... 690 V 3 AC, TT/TN or IT
SINAMICS G180
compact units
6SE0100-
1A
■
21-0
■
A7
6SE0100-
1A
■
21-3
■
A7
6SE0100-
1A
■
21-8
■
A7
6SE0100-
1A
■
22-5
■
A7
6SE0100-
1A
■
23-4
■
A7
Converter type
2T2A-07600-007
2T2A-07600-011
2T2A-07600-015
2T2A-07600-022
2T2A-07600-030
Electrical data at motor end
Type rating
1)
• at 50 Hz 690 V
kW
7.5
11
15
22
30
• at 60 Hz 575 V
hp
8
12
17
25
34
Output voltage
2)
V
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
Output current
• Continuous current
A
9.5
13
18
27
36
• Short-time current
(60 s every 10 minutes) max.
A
11
16
21
33
45
Overload capability
(60 s every 10 minutes) max.
%
16
23
17
22
25
Output power
kVA
11.4
15.5
21.5
32.3
43
Output frequency, max.
Hz
250
250
250
250
250
Rated clock cycle
kHz
3
3
3
3
3
adjustable from
kHz
2 ... 5
2 ... 5
2 ... 5
2 ... 5
2 ... 5
Power loss
3)
kW
0.29
0.4
0.55
0.74
1
Rated efficiency
%
96.7
96.8
96.8
97.0
97.0
Electrical data at line end
Connected load
kVA
3.7
4.6
6.4
8.6
12.1
Rated input voltage
V
690
690
690
690
690
Input current
• Continuous line current
A
8.8
11.8
16.8
25.3
37.3
• Short-time line current (60 s)
max.
A
10
14
20
31
47
Line fuse
(provided by customer)
gL (A)
10 ... 32
16 ... 32
20 ... 32
32
40 ... 63
λ
line
0.94
0.948
0.94
0.948
0.867
Cos
ϕ
line
1
1
1
1
1
Radio interference suppres-
sion acc. to EN 61800-3
4)
C2 (class A filter)
C2 (class A filter)
C2 (class A filter)
C2 (class A filter)
C2 (class A filter)
Mechanical data
Coolant requirements
m
3
/h
90
90
130
130
750
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
60
60
60
60
60
Max. cable length between
converter and motor with
standard insulation
• (shielded)
m
300
5)
300
5)
300
5)
300
5)
300
5)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections,
see "Cable cross-sections and
connections" in section
"Configuring instructions"
Dimensions
• Width
mm
225
225
225
225
350
• Height
(without mounting brackets)
mm
610
610
610
610
710
• Depth
mm
320
320
320
320
320
Weight, approx.
kg
26
26
28
28
55
Approvals, according to
NRTL
6)
NRTL
6)
NRTL
6)
NRTL
6)
NRTL
6)
Frame size
K3
K3
K3
K3
K4
1)
Rated power of a typical 2- to 6-pole standard motor.
2)
Typical output voltage dependent on filter and unit type.
3)
Maximum power loss with continuous current.
4)
EMC filter not required for IT system, in which case RI suppression
category C4.
5)
Value is applicable with option L10 (strengthened d
v
/d
t
filter;
strengthened filter is integrated in unit).
6)
On request; the voltage range for NRTL units ends at max. 600 V.
© Siemens AG 2014