SIEMENS
SINAMICS G180
SINAMICS G180 compact units and SINAMICS G180 cabinet systems
SINAMICS G180 compact units
2/11
Siemens D 18.1 · 2014
2
■
Technical data
(continued)
500 V, 6-pulse
(continued)
Line voltage, supply system type
230 ... 500 V 3 AC, IT
SINAMICS G180
compact units
6SE0100-
1AD32-1
■
A7
6SE0100-
1AD32-5
■
A7
6SE0100-
1AD33-0
■
A7
Converter type
2T2A-07500-132
2T2A-07500-160
2T2A-07500-200
Electrical data at motor end
Type rating
1)
• at 50 Hz 500 V
kW
132
160
200
• at 60 Hz 460 V
hp
163
197
247
Output voltage
2)
V
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
Output current
• Continuous current
A
205
245
295
• Short-time current
(60 s every 10 minutes) max.
A
240
300
360
Overload capability
(60 s every 10 minutes) max.
%
17
22
22
Output power
kVA
178
212
256
Output frequency, max.
Hz
250
250
250
Rated clock cycle
kHz
3
3
3
adjustable from
kHz
2 ... 5
2 ... 5
2 ... 5
Power loss
3)
kW
3.84
4.48
5.6
Rated efficiency
%
97.3
97.4
97.4
Electrical data at line end
Connected load
kVA
161
197
3.8
Rated input voltage
V
500
500
500
Input current
• Continuous line current
A
196
237
286
• Short-time line current (60 s)
max.
A
230
290
349
Line fuse
(provided by customer)
gL (A)
200 ... 250
250 ... 315
315 ... 400
λ
line
0.912
0.912
0.912
Cos
ϕ
line
1
1
1
Radio interference suppres-
sion acc. to EN 61800-3
C4
C4
C4
Mechanical data
Coolant requirements
m
3
/h
1050
1600
1600
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
66
66
60
Max. cable length between
converter and motor with
standard insulation
• (shielded)
m
300
4)
300
4)
300
4)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections,
see "Cable cross-sections and
connections" in section
"Configuring instructions"
Dimensions
• Width
mm
350
500
500
• Height
(without mounting brackets)
mm
1060
1060
1060
• Depth
mm
320
320
320
Weight, approx.
kg
96
170
180
Approvals, according to
NRTL
5)
NRTL
5)
NRTL
5)
Frame size
K5
K6
K6
1)
Rated power of a typical 2- to 6-pole standard motor.
2)
Typical output voltage dependent on filter and unit type.
3)
Maximum power loss with continuous current.
4)
Option L10 included (strengthened d
v
/d
t
filter; strengthened filter is
integrated in unit).
5)
On request
© Siemens AG 2014