SIEMENS
SINAMICS G180
SINAMICS G180 compact units and SINAMICS G180 cabinet systems
SINAMICS G180 compact units
2/10
Siemens D 18.1 · 2014
2
■
Technical data
(continued)
500 V, 6-pulse
(continued)
Line voltage, supply system type
230 ... 500 V 3 AC, IT
SINAMICS G180
compact units
6SE0100-
1AD27-8
■
A7
6SE0100-
1AD28-8
■
A7
6SE0100-
1AD31-1
■
A7
6SE0100-
1AD31-5
■
A7
6SE0100-
1AD31-8
■
A7
Converter type
2T2A-07500-045
2T2A-07500-055
2T2A-07500-075
2T2A-07500-090
2T2A-07500-110
Electrical data at motor end
Type rating
1)
• at 50 Hz 500 V
kW
45
55
75
90
110
• at 60 Hz 460 V
hp
56
68
93
111
136
Output voltage
2)
V
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
Output current
• Continuous current
A
78
88
110
145
175
• Short-time current
(60 s every 10 minutes) max.
A
88
110
126
165
204
Overload capability
(60 s every 10 minutes) max.
%
13
25
15
14
17
Output power
kVA
67.5
76.2
95.3
126
152
Output frequency, max.
Hz
250
250
250
250
250
Rated clock cycle
kHz
3
3
3
3
3
adjustable from
kHz
2 ... 5
2 ... 5
2 ... 5
20 ... 5
2 ... 5
Power loss
3)
kW
1.59
1.8
2.37
2.83
3.33
Rated efficiency
%
96.8
97.0
97.1
97.1
97.2
Electrical data at line end
Connected load
kVA
57.5
74.8
98.4
119
136
Rated input voltage
V
500
500
500
500
500
Input current
• Continuous line current
A
73.7
87.6
109
143
170
• Short-time line current (60 s)
max.
A
83
110
125
163
198
Line fuse
(provided by customer)
gL (A)
80 ... 100
100
125
160
200
λ
line
0.918
0.912
0.918
0.918
0.908
Cos
ϕ
line
1
1
1
1
1
Radio interference suppres-
sion acc. to EN 61800-3
C4
C4
C4
C4
C4
Mechanical data
Coolant requirements
m
3
/h
750
750
750
1050
1050
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
62
62
64
64
64
Max. cable length between
converter and motor with
standard insulation
• (shielded)
m
300
4)
300
4)
300
4)
300
4)
300
4)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections,
see "Cable cross-sections and
connections" in section
"Configuring instructions"
Dimensions
• Width
mm
350
350
350
350
350
• Height
(without mounting brackets)
mm
710
710
710
1060
1060
• Depth
mm
320
320
320
320
320
Weight, approx.
kg
51
53
55
90
94
Approvals, according to
NRTL
5)
NRTL
5)
NRTL
5)
NRTL
5)
NRTL
5)
Frame size
K4
K4
K4
K5
K5
1)
Rated power of a typical 2- to 6-pole standard motor.
2)
Typical output voltage dependent on filter and unit type.
3)
Maximum power loss with continuous current.
4)
Option L10 included (strengthened d
v
/d
t
filter; strengthened filter is
integrated in unit).
5)
On request
© Siemens AG 2014