Siemens D 18.1 · 2014
2
■
Technical data
(continued)
500 V, 6-pulse
(continued)
Line voltage, supply system type
230 ... 500 V 3 AC, IT
SINAMICS G180
compact units
6SE0100-
1AD21-8
■
A7
6SE0100-
1AD22-5
■
A7
6SE0100-
1AD23-7
■
A7
6SE0100-
1AD24-8
■
A7
6SE0100-
1AD25-8
■
A7
Converter type
2T2A-07500-011
2T2A-07500-015
2T2A-07500-022
2T2A-07500-030
2T2A-07500-037
Electrical data at motor end
Type rating
1)
• at 50 Hz 500 V
kW
11
15
22
30
37
• at 60 Hz 460 V
hp
17
23
34
46
57
Output voltage
2)
V
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
Output current
• Continuous current
A
18
24.5
37
48
58
• Short-time current
(60 s every 10 minutes) max.
A
20
27
44
54
63
Overload capability
(60 s every 10 minutes) max.
%
11
10
19
13
9
Output power
kVA
15.6
21.2
32
41.6
50.2
Output frequency, max.
Hz
250
250
250
250
250
Rated clock cycle
kHz
4.5
4.5
4.5
4.5
4.5
adjustable from
kHz
3 ... 7.5
3 ... 7.5
3 ... 7.5
3 ... 7.5
3 ... 7.5
Power loss
3)
kW
0.48
0.63
0.89
1.17
1.35
Rated efficiency
%
96.2
96.3
96.4
96.5
96.7
Electrical data at line end
Connected load
kVA
16
24.4
32
39.2
52.3
Rated input voltage
V
500
500
500
500
500
Input current
• Continuous line current
A
17.4
23.4
35.8
46.8
57.1
• Short-time line current (60 s)
max.
A
19
26
43
53
62
Line fuse
(provided by customer)
gL (A)
20 ... 32
25 ... 32
40 ... 80
50 ... 80
63 ... 80
λ
line
0.902
0.924
0.918
0.924
0.912
Cos
ϕ
line
1
1
1
1
1
Radio interference suppres-
sion acc. to EN 61800-3
C4
C4
C4
C4
C4
Mechanical data
Coolant requirements
m
3
/h
90
130
280
280
280
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
60
60
60
60
62
Max. cable length between
converter and motor with
standard insulation
• (shielded)
m
300
4)
300
4)
300
4)
300
4)
300
4)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections,
see "Cable cross-sections and
connections" in section
"Configuring instructions"
Dimensions
• Width
mm
165
165
225
225
225
• Height
(without mounting brackets)
mm
510
510
610
610
610
• Depth
mm
320
320
320
320
320
Weight, approx.
kg
16.5
17.5
30
32
32
Approvals, according to
NRTL
5)
NRTL
5)
NRTL
5)
NRTL
5)
NRTL
5)
Frame size
K2
K2
K3
K3
K3
1)
Rated power of a typical 2- to 6-pole standard motor.
2)
Typical output voltage dependent on filter and unit type.
3)
Maximum power loss with continuous current.
4)
Option L10 included (strengthened d
v
/d
t
filter; strengthened filter is
integrated in unit).
5)
On request
© Siemens AG 2014