SIEMENS
SINAMICS G180
Configuring instructions
Standard interface
5/17
Siemens D 18.1 · 2014
5
■
Overview
(continued)
Standard assignment of inputs/outputs
The following table shows the default assignments of the
interface for a "standard" application.
NAMUR-compliant assignment of inputs/outputs
The following table shows the default assignments of the
interface for a "NAMUR" application.
Signal designation
Function
Digital input signals of module "CB08"
Internal digital input 8
Controller enable global 1
Internal digital input 9
Freely parameterizable
Internal digital input 10
Speed ON remote
Internal digital input 11
Freely parameterizable
Internal digital input 12
Local/remote, remote=1
Internal digital input 13
External fault
Internal digital input 14
Remote reset
Internal digital input 15
Rapid stop global 1
Internal digital input 16
Reverse remote
Internal digital input 27
PTC thermistor trip
(not for explosion-proof motors)
Internal digital input 28
PTC thermistor prewarning
(not for explosion-proof motors)
Internal digital input 29
External warning
Digital output signals of module "CB08"
Internal digital output 37, 38, 39
Relay 1: "Ready"
Internal digital output 41, 42
Relay 2: "Operation"
Internal digital output 30, 31
Relay 3: "Alarm"
Internal digital output 32, 33
Relay 4: Not assigned
Internal digital output 34, 35, 36
"Converter fault"
Analog input signals of module "CB08"
Internal analog input 50, 51, 52
Speed setpoint
Internal analog input 53, 54
User-assignable connection
Analog output signals of module "CB08"
Internal analog output 60, 61
Motor speed
Internal analog output 62, 63
Motor current
Signal designation
Function
Digital input signals of module "CB08"
Internal digital input 8
Main contactor checkback
Internal digital input 9
Test/Normal switch on converter
Internal digital input 10
ON/OFF static; ON dynamic
(controller enable ON)
Internal digital input 11
OFF dynamic
(controller enable OFF)
Internal digital input 12
Fast
(motorized potentiometer UP)
Internal digital input 13
Slow
(motorized potentiometer DOWN)
Internal digital input 14
Reset normal
Internal digital input 15
Interlock (controller disable)
Internal digital input 16
Reverse normal
Internal digital input 27
Freely parameterizable
Internal digital input 28
Freely parameterizable
Internal digital input 29
Freely parameterizable
Digital output signals of module "CB08"
Internal digital output 37, 38, 39
Relay 1: "Group prewarning"
Internal digital output 41, 42
Relay 2: "Main(line)contactor closed"
Internal digital output 30, 31
Relay 3: "Ready"
Internal digital output 32, 33
Relay 4: "Motor turning"
Internal digital output 34, 35, 36
"Converter fault"
Analog input signals of module "CB08"
Internal analog input 50, 51, 52
Speed setpoint
(terminal 50/51 or 52/51)
Internal analog input 53, 54
Actual process value/user-assign-
able input (terminal 53/51 or 54/51)
Analog output signals of module "CB08"
Internal analog output 60, 61
Motor speed
Internal analog output 62, 63
Motor current