SIEMENS
SINAMICS G180
SINAMICS G180 compact units and SINAMICS G180 cabinet systems
SINAMICS G180 compact units
2/4
Siemens D 18.1 · 2014
2
■
Technical data
(continued)
400 V, 6-pulse
Line voltage, supply system type
230 ... 500 V 3 AC, TT/TN
SINAMICS G180
compact units
6SE0100-
1AC15-5
■
A7
6SE0100-
1AC17-0
■
A7
6SE0100-
1AC21-0
■
A7
6SE0100-
1AC21-3
■
A7
6SE0100-
1AC21-8
■
A7
Converter type
2T2A-07400-002
2T2A-07400-003
2T2A-07400-004
2T2A-07400-005
2T2A-07400-007
Electrical data at motor end
Type rating
1)
• at 50 Hz 400 V
kW
2.2
3
4
5.5
7.5
• at 60 Hz 460 V
hp
3
5
6
9
12
Output voltage
2)
V
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
Output current
• Continuous current
A
5.5
7
9.5
13
18
• Short-time current
(60 s every 10 minutes) max.
A
6.5
8
11
15
20
Overload capability
(60 s every 10 minutes) max.
%
18
14
16
15
11
Output power
kVA
3.8
4.8
6.6
9
12.5
Output frequency, max.
Hz
250
250
250
250
250
Rated clock cycle
kHz
4.5
4.5
4.5
4.5
4.5
adjustable from
kHz
3 ... 7.5
3 ... 7.5
3 ... 7.5
3 ... 7.5
3 ... 7.5
Power loss
3)
kW
0.13
0.16
0.2
0.26
0.33
Rated efficiency
%
95.2
95.8
95.9
96
96.2
Electrical data at line end
Connected load
kVA
3.7
4.5
6.2
8.5
12
Rated input voltage
V
400
400
400
400
400
Input current
• Continuous line current
A
5.3
6.5
8.9
12.2
17.3
• Short-time line current (60 s)
max.
A
6.3
7.4
10
14
19
Line fuse
(provided by customer)
gL (A)
6 … 16
10 ... 16
10 ... 16
16
20 ... 32
λ
line
0.927
0.94
0.918
0.937
0.918
Cos
ϕ
line
1
1
1
1
1
Radio interference suppres-
sion acc. to EN 61800-3
C2 (class A filter)
C2 (class A filter)
C2 (class A filter)
C2 (class A filter)
C2 (class A filter)
Mechanical data
Coolant requirements
m
3
/h
45
45
90
90
90
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
60
60
60
60
60
Max. cable length between
converter and motor with
standard insulation
• on systems
≤
400 V (shielded)
m
200/350
4)
200/350
4)
200/350
4)
200/350
4)
200/350
4)
• on systems > 400 V (shielded)
m
150/300
4)
150/300
4)
150/300
4)
150/300
4)
150/300
4)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections,
see "Cable cross-sections and
connections" in section
"Configuring instructions"
Dimensions
• Width
mm
165
165
165
165
165
• Height
(without mounting brackets)
mm
410
410
410
410
510
• Depth
mm
320
320
320
320
320
Weight, approx.
kg
11.5
11.5
11.5
11.5
16.5
Approvals, according to
NRTL
5)
NRTL
5)
NRTL
5)
NRTL
5)
NRTL
5)
Frame size
K1
K1
K1
K1
K2
1)
Rated power of a typical 2- to 6-pole standard motor.
2)
Typical output voltage dependent on filter and unit type.
3)
Maximum power loss with continuous current.
4)
Value is applicable with option L10 (strengthened d
v
/d
t
filter;
strengthened filter is integrated in unit).
5)
On request
© Siemens AG 2014