SIEMENS
SINAMICS G180
Configuring instructions
Cable cross-sections and connections
5/13
Siemens D 18.1 · 2014
5
■
Overview
(continued)
Note:
Device cable lugs must be used to connect cables to the main
switch or circuit breaker. These cable lugs are narrower, for
example, than DIN cable lugs. The lugs are not normally supplied
with the converter since they are generally provided by the cable
installer.
It is generally possible to request a customized line connection
or motor connection, see "Engineer To Order – ETO" under "Option
descriptions" on Page 4/34. Please ask your Siemens contact
person for further details.
Type
rating
Converter
Converter type
Line connection
(standard)
Line connection
with main
switch or circuit breaker
(Options:
S01
,
S02
,
S03
,
S04
,
S06
,
S08
,
S09
,
S11
,
S12
,
S21
,
S22
,
S23
,
S24
,
S41
)
Motor connection
SINAMICS G180
Cable cross-
section
solid/stranded
Fixing
Cable cross-
section
solid/stranded
Fixing
Cable cross-
section
solid/stranded
Fixing
min.
max.
min.
max.
min.
max.
kW
IEC
mm²
IEC
mm²
IEC
mm²
IEC
mm²
IEC
mm²
IEC
mm²
SINAMICS G180 cabinet units 690 V 18-pulse, air-cooled and liquid-cooled (3 × 400 to 600
1)
/690 V 3 AC IT system, 50 to 60 Hz)
2000
6SE01.0-3DH42-2.A7
2T.K-.7603-920
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
12 × 10
24 × 150
12 × 120
24 × 300
3 × 4 × M12
2300
6SE01.0-3DH42-4.A7
2T.K-.7603-923
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
12 × 10
24 × 150
12 × 120
24 × 300
3 × 4 × M12
2600
6SE01.0-3DH42-7.A7
2T.K-.7603-926
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
12 × 10
24 × 150
12 × 120
24 × 300
3 × 4 × M12
2900
6SE01.0-3DH43-0.A7
2T.K-.7603-929
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
12 × 10
24 × 150
12 × 120
24 × 300
3 × 4 × M12
4100
6SE01.0-3HH44-3.A7
2T.K-.7606-941
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
24 × 10
48 × 150
24 × 300
48 × 300
6 × 4 × M12
4100
6SE01.0-3HH44-8.A7
2T.K-.7606-947
2)
2)
2)
24 × 10
48 × 150
24 × 300
48 × 300
6 × 4 × M12
5300
6SE01.0-3HH45-4.A7
2T.K-.7606-953
2)
2)
2)
24 × 10
48 × 150
24 × 300
48 × 300
6 × 4 × M12
5800
6SE01.0-3HH46-0.A7
2T.K-.7606-958
2)
2)
2)
24 × 10
48 × 150
24 × 300
48 × 300
6 × 4 × M12
SINAMICS G180 cabinet units 690 V 24-pulse, air-cooled and liquid-cooled (4 × 400 to 600
1)
/690 V 3 AC IT system, 50 to 60 Hz)
1200
6SE01.0-4CH41-2.A7
2T.L-.7602-912
2 × 6
2 × 300
1 × M10
8 × 10
16 × 150
8 × 300
16 × 300
2 × 4 × M12
1300
6SE01.0-4CH41-3.A7
2T.L-.7602-913
2 × 6
2 × 300
1 × M10
8 × 10
16 × 150
8 × 300
16 × 300
2 × 4 × M12
1500
6SE01.0-4CH41-5.A7
2T.L-.7602-915
2 × 6
2 × 300
1 × M10
8 × 10
16 × 150
8 × 300
16 × 300
2 × 4 × M12
1100
6SE01.0-4CH41-7.A7
2T.L-.7602-917
2 × 6
2 × 300
1 × M10
8 × 10
16 × 150
8 × 300
16 × 300
2 × 4 × M12
1900
6SE01.0-4CH42-0.A7
2T.L-.7602-919
2 × 6
2 × 300
1 × M10
8 × 10
16 × 150
8 × 300
16 × 300
2 × 4 × M12
3100
6SE01.0-4EH43-2.A7
2T.L-87604-931
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
16 × 10
32 × 150
16 × 120
32 × 300
4 × 4 × M12
3500
6SE01.0-4EH43-6.A7
2T.L-87604-935
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
16 × 10
32 × 150
16 × 120
32 × 300
4 × 4 × M12
3900
6SE01.0-4EH44-0.A7
2T.L-87604-939
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
16 × 10
32 × 150
16 × 120
32 × 300
4 × 4 × M12
4100
6SE01.0-4HH44-3.A7
2T.L-87606-941
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
24 × 10
48 × 150
24 × 300
48 × 300
6 × 4 × M12
4100
6SE01.0-4HH44-8.A7
2T.L-87606-947
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
24 × 10
48 × 150
24 × 300
48 × 300
6 × 4 × M12
5300
6SE01.0-4HH45-4.A7
2T.L-87606-953
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
24 × 10
48 × 150
24 × 300
48 × 300
6 × 4 × M12
5800
6SE01.0-4HH46-0.A7
2T.L-87606-958
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
24 × 10
48 × 150
24 × 300
48 × 300
6 × 4 × M12
1)
With an NRTL unit ("U" in 14th position of article number), the voltage range
ends at max. 600 V, otherwise at 690 V.
2)
On request.
© Siemens AG 2014